08: Bypass mode setting
09: Battery backup time setting
10: Reserved
11: Reserved
Parameter 2:
OPN:
Bypass allowed. When selected, UPS
will run at Bypass mode depending on bypass
enabled/disabled setting.
FBD:
Bypass not allowed. When selected, it's
not allowed for running in Bypass mode under
any situations.
Parameter 3:
ENA:
Bypass enabled. When selected, Bypass
mode is activated.
DIS:
Bypass
disabled.
automatic bypass is acceptable, but manual
bypass is not allowed. Manual bypass means
users manually operate UPS for Bypass mode.
For example, press OFF button in AC mode to
turn into Bypass mode.
Parameter 3:
000~999:
Set the maximum backup time
from 0 min to 999 min. UPS will shut down to
protect battery after backup time arrives.
DIS:
Disable battery discharge protection and
backup time will depend on battery capacity.
The default value is DIS.
Reserved
Reserved
When
selected,
29