NOTE!
If the UPS is set to CVCF mode, the bypass function will be disabled automatically.
When used in CVCF mode, the power of the UPS is de-rated to 60%.
But when a single UPS without parallel function is powered on with mains and
before the UPS finished the startup, there will be a few seconds of voltage pulse
(same as the input voltage) on the bypass output. For the UPS with parallel
function, this pulse situation won't happen.
03: Voltage range for bypass
04: Frequency range for bypass
NCF:
Setting UPS to normal mode (not CVCF
mode). If selected, the output frequency will
synchronize with the input frequency within
46~54 Hz at 50Hz or within 56~64 Hz at
60Hz according to setting in parameter 2. If 50
Hz selected in parameter 2, UPS will transfer
to battery mode when input frequency is
not within 46~54 Hz. If 60Hz selected in
parameter 2, UPS will transfer to battery mode
when input frequency is not within 56~64 Hz.
*If Parameter 2 is ATO, the Parameter 3 will
show the current frequency.
Parameter 2:
Set the acceptable low voltage for
bypass. Setting range is from 110V to 209V and
the default value is 110V.
Parameter 3:
Set the acceptable high voltage for
bypass. Setting range is from 231V to 276V and
the default value is 264V.
Parameter 2:
Set the acceptable low frequency
for bypass.
50 Hz system: Setting range is from 46.0Hz to
49.0Hz.
60 Hz system: Setting range is from 56.0Hz to
59.0Hz.
The default value is 46.0Hz/56.0Hz.
Parameter 3:
Set the acceptable high frequency
for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
27