Specifications; Iq8P-72-2-Int Microinverters - enphase IQ8P Installation And Operation Manual

Microinverters
Hide thumbs Also See for IQ8P:
Table of Contents

Advertisement

Specifications

Refer the specifications in the following table for the following IQ8P Microinverters

IQ8P-72-2-INT Microinverters

INPUT DATA (DC)
Typical module
compatibility
Minimum/Maximum
input voltage
Start-up input voltage
Rated input voltage
Minimum/Maximum
MPP voltage
Minimum/Maximum
operating voltage
Maximum input
current
Maximum short-
circuit DC input
current
Maximum input
power
1
OUTPUT DATA (AC)
Maximum apparent
power
Rated power
Nominal grid voltage
Minimum/Maximum
grid voltage
Maximum output
current
Nominal frequency
29
IQ8P Microinverter Installation and Operation Manual
UNITS
U
/U
V
dcmin
dcmax
U
V
dcstart
U
V
dc,r
U
/U
V
mppmin
mppmax
U
/U
V
opmin
opmax
I
A
dcmax
I
A
scmax
P
W
dcmax
UNITS
S
VA
ac, max
P
W
ac, r
U
V
acnom
U
/U
V
acmin
acmax
I
A
acmax
f
Hz
nom
© 2023 Enphase Energy Inc. All rights reserved.
IQ8P-72-2-INT
60-cell/120-half-cell, 66-cell/132-half-cell, 72-
cell/144-half-cell, 78-cell/156-half-cell
No enforced DC/AC ratio and maximum input power.
Modules can be paired as long as the maximum input
voltage is not exceeded and the maximum input
current of the inverter at the lowest and highest
temperatures is respected. See the compatibility
calculator at
https://enphase.com/en-
za/installers/microinverters/calculator.
36/55
IQ8P-72-2-INT
184/276
16/65
22
45.5
16/65
14
25
670
480
475
230
2.09
50
September 2023
IOM-00001-1.0