Data Report; Example Of Reportdatacmd - netvox R718N360 User Manual

Wireless 3-phase current meter interface
Hide thumbs Also See for R718N360:
Table of Contents

Advertisement

5. Data Report

Before any configuration is made, the device sends data according to the default configuration.
The device will immediately send a version packet report along with two uplink packets including battery voltage and raw data of
three-phase current.
Default setting:
Maximum time: Max Interval =60 min (3600 s)
Minimum time: Min Interval =60 min (3600 s)
*The interval between min time and max time must be greater than 20 seconds.
Note:
(1) The device report interval will be programmed based on the default firmware which may vary.
(2) If the MinTime configuration is less than 20 seconds, it will configure 20 seconds.
(3) R718N360 series would take about 3 seconds for the CT to sample and process the collected value, If the current changes
frequently, the sampling result might be wrong.
Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver
http://cmddoc.netvoxcloud.com/cmddoc
Data report configuration and sending period are as follows:
Min. Interval
(Unit: second)
Any number between
1 to 65535

5.1 Example of ReportDataCmd

Fport: 0x06
Bytes
Version– 1 bytes –0x01——the Version of NetvoxLoRaWAN Application Command Version
DeviceType – 1 byte – Device Type of Device
The devicetype is listed in Netvox LoRaWAN Application Devicetype V1.9.doc
ReportType – 1 byte –the Presention of the NetvoxPayLoadData,according the devicetype
NetvoxPayLoadData– Fixed bytes (Fixed =8bytes)
to resolve uplink data.
Max. Interval
(Unit: second)
Any number between
1 to 65535
1
Version
Reportable Change
Reportable Change
Can not be 0.
1
DeviceType
ReportType
5
Current Change≥
Report
per Min. Interval
1
Var (Fix=8 Bytes)
NetvoxPayLoadData
Current Change<
Reportable Change
Report
per Max. Interval