CHAP.07 POSITIONING AND CONNECTIONS FOR THE INSTALLER

07.1

SETTING UP OF EXTERNAL AIR INTAKES AND ELECTRIC CURRENT

max 1250
1
4
150
- View from the back (main quotes for carrying out installation)
NOTE
The external air intakes must be made so that they cannot get accidentally covered and if they have an insect
protection mesh they must be cleaned periodically to prevent clogging with dust and dirt, especially in periods with intense
pollen concentrations.
The device must only be installed indoors and on surfaces
Front view
that can support the load. If the existing construction does not
meet this requirement, it will be necessary to take appropriate
measures (e.g. installing a load distribution plate). The appliance
must be installed in an area where the appliance itself, gas
exhaust pipes and flue can be easily accessed for maintenance.
Fig. 1 illustrates minimum distances that must be observed, all
measures must be in mm.
The lateral distance from the adjacent wall, according to
installation, is to be maintained on both sides.
1.
2.
2
3
3.
4.
View from
above
NOTE
NOTE
900
Electrical socket
External air inlet (see chap. 07.4)
Rear panel
Side panel
As indicated in the national reference standard UNI
10683:2012, the product can not be installed in
rooms with a volume of under 15 m
Bear in mind that the minimum distances from
inflammable materials are:
Minimum air distance from inflammable side wale: 150 mm
Minimum air distance from inflammable rear wall: 100 mm
Frontal air distance from inflammable material: 900 mm
as indicated in CHAP.06.1 - HOMOLOGATION
.