Quick Start Guide
Step 4: Installation
Flanged sensors
Gaskets
The sensor requires a gasket at each of its connections to adjacent devices or piping.
The gasket material selected must be compatible with the process fluid and operating
conditions. Gaskets are required on each side of a grounding ring. All other
applications (including sensors with lining protectors or a grounding electrode)
require only one gasket on each end connection.
Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the
sensor. If spiral wound or metallic gaskets are required for the application, lining protectors
must be used.
Figure 8. Flanged gasket placement