Magnetic flowmeter system

Advertisement

February 2014
To order cable specify length as quantity desired.
25 feet = Qty (25) 08732-0753-1003
Table 5. Cable requirements
Description
Coil Drive Cable (14 AWG)
Belden 8720, Alpha 2442
or equivalent
Electrode Cable (20 AWG)
Belden 8762, Alpha 2411
or equivalent
Combination Cable
Coil Drive Cable (18 AWG) and
Electrode Cable (20 AWG)
Potential Shock Hazard Across Terminals 1 & 2 (40 VAC).
Wiring the transmitter to the sensor
When using individual cables for coil drive and electrode refer to
the combination coil drive and electrode cable, refer to
on page 20
1. Connect the coil drive cable using terminals 1, 2, and 3.
2. Connect the electrode cable using terminals 17, 18, and 19
Table 6. Individual coil and electrode cables
Transmitter terminal
1
2
3
17
18
19
for transmitter specific wiring diagrams.
Sensor terminal
1
2
3
17
18
19
Length
Part number
ft
08712-0060-0001
m
08712-0060-2013
ft
08712-0061-0001
m
08712-0061-2003
ft
08732-0753-1003
m
08732-0753-2004
Table 7
Wire gauge
14
14
14
20
20
20
Quick Start Guide
Table 6
. If using
Figure 16
. See
Wire color
Clear
Black
Shield
Shield
Black
Clear
19