Prerequisites for connecting the inverter
Permissible
Cables with the following design can be connected to the terminals of the invert-
cables for the
er:
electrical con-
nection
Grid connections with push-in terminal*
Select a sufficiently large cable cross section based on the actual device output!
Power
categories
3 - 6 kW
2.5 - 10 mm
(3-pin)
AWG 14-8
Grid connections backup power with push-in terminal*
Select a sufficiently large cable cross section based on the actual device output.
Power
categories
3 - 6 kW
1.5 - 10 mm
(3-pin)
AWG 16-8
PV/BAT connections with push-in terminal**
Select a sufficiently large cable cross section based on the actual device output.
Power
categories
3 - 6 kW
4 - 10 mm
(2 x 5-pin)
AWG 12-8
Ground electrode terminal (6-pin)
Select a sufficiently large cable cross section based on the actual device output.
Number of
pins
2.5 - 16 mm
2
AWG 14-6
2.5 - 10 mm
4
AWG 14-8
*
**
-
Copper: round, solid
-
Copper: round, fine-stranded, up to conductor class 4
Solid
Multi-stranded
2
2.5 - 10 mm
AWG 14-8
Solid
Multi-stranded
2
1.5 - 10 mm
AWG 16-8
Solid
Multi-stranded
2
4 - 10 mm
AWG 12-8
Solid
Multi-stranded
2
2.5 - 16 mm
AWG 14-6
2
2.5 - 10 mm
AWG 14-8
According to product standard IEC 62109, the ground conductor must
correspond to the phase cross-section for phase cross-sections ≤16 mm²;
for phase cross-sections >16 mm², it must correspond to at least 16 mm².
The cable cross section must be dimensioned in accordance with the in-
stallation situation and the specifications of the battery manufacturer.
Fine-stranded with ferrules‐
Fine-stranded
2
2
2.5 - 10 mm
AWG 14-8
Fine-stranded with ferrules‐
Fine-stranded
2
2
1.5 - 10 mm
AWG 16-8
Fine-stranded with ferrules‐
Fine-stranded
2
2
4 - 10 mm
AWG 12-8
Fine-stranded with ferrules‐
Fine-stranded
2
2
2.5 - 16 mm
AWG 14-6
2
2
2.5 - 10 mm
AWG 14-8
with/without collar
2
2.5 - 6 mm
AWG 14-10
with/without collar
2
1.5 - 6 mm
AWG 16-10
with/without collar
2
4 - 6 mm
AWG 12-10
with/without collar
2
2.5 - 16 mm
AWG 14-6
2
2.5 - 10 mm
AWG 14-8
65