Turn off the automatic circuit breaker.
Make sure that the DC disconnector is
in the "Off" switch setting.
Loosen the five screws of the connec-
tion area cover by rotating them 180°
to the left using a screwdriver (TX20).
Remove the connection area cover
from the device.
Guide the mains cable from below
through the strain-relief device on the
right side.
Remove the AC terminal.
IMPORTANT!
The ground conductor must be con-
nected with a loop so that if the strain-
relief device fails, the ground conduct-
or is disconnected last.
For more information on the strain-re-
lief device, see chapter
of the AC cable
on page 66.
Strip the insulation of the single con-
ductors by 12 mm.
Select the cable cross section in ac-
cordance with the instructions in
missible cables for the electrical con-
nection
from page 65.
Lift to open the terminal's operating
lever and insert the stripped single
conductor into the slot provided as far
as it will go.
Then close the terminal's operating
lever until it engages.
NOTE!
Only one conductor may be connected
to each pin.
The AC cables can be connected to
the AC terminals without ferrules.