off. In the case of different thresholds, the I/O with the lowest threshold is
switched on first, followed by the second lowest, and so on.
I/Os controlled by the produced power are always prioritised over a battery and
Fronius Ohmpilot. That is to say that an I/O can switch on and result in the bat-
tery no longer being charged or the Fronius Ohmpilot no longer being activated.
IMPORTANT!
An I/O is activated/deactivated only after 60 seconds.
"Load"
-
Control is
"Off"
(disabled).
-
Control is effected by the
-
Control is effected by
only be selected if a meter has been connected. Control is effected using the
actual power of feeding in with respect to the grid.
"Thresholds"
-
"On": For entering an effective power limit, at which the output is activated.
"Off": For entering an effective power limit, at which the output is deactiv-
-
ated.
"Duration"
-
Field for enabling
"Minimum duration per
which the output is to be activated for each switch-on process.
-
Field for activating the
-
Field for enabling a
ated in total per day (total of several switch-on processes).
"Power
Production".
"Power Surplus"
(given feed limits). This option can
on-signal", a minimum duration for
"Maximum duration per
"Desired duration"
for which the output is to be activ-
day".
117