Pwm Duty Cycle; Duty Cycle - Deif AGC-4 Mk II Quick Start Manual

Analogue controller and transducer outputs
Hide thumbs Also See for AGC-4 Mk II:
Table of Contents

Advertisement

Menu Value
5900 I
5910
U
5920 f
5930 Input 102
5940 Input 105
5950 Input 108
5960 P total consumed The total power produced in the power management system.
5970
P total available
*Note: P1, P2 and P3 are identical. For example, P1 can be used as an input to a switchboard instrument, while P2 can be an
input to a PLC.
Available power transducer setup example
To set up transducer 66 to transmit the available power (0 to 10 MW) as a 4 to 20 mA signal:
In menu 5973, for Set point, select 4-20mA. For Transducer A, select Transducer 66.
In menu 5975, select the minimum value (this corresponds to 4 mA), that is, 0 kW.
In menu 5974, select the maximum value (this corresponds to 20 mA), that is, 10000 kW.
NOTE
These values are also available through Modbus.
2.2

PWM duty cycle

2.2.1

Duty cycle

The PWM signal has a frequency of 500 Hz ±50 Hz. The resolution of the duty cycle is 12 bits, which gives 4095 output
levels. The output is an open collector output with a 1 kΩ pull-up resistor.
The low level of the signal is between 0 and 0.5 volts, and the high level is between 5.7 and 6 volts.
Voltage
5.7...6 V
0 0.5 V
Options E F AGC-4 Mk II 4189341277C EN
Details
Genset L1 current
Busbar L1-L2 voltage
Busbar frequency
The value received by analogue input 102.
The value received by analogue input 105.
The value received by analogue input 108.
The additional power that the power management system could supply without starting more
gensets.
0 100 % duty
cycle
Time
Page 9 of 10