Number Of Tanks (Nt); Tank In Service (Ts); Unit Capacity (C) - Pentair FLECK 4600-SXT Installer Manual

Table of Contents

Advertisement

6.5.6. Number of tanks (NT)

Select the number of tanks.
Options:
NT 1: Single tank system;
NT 2: Double tanks system.
Mandatory
Due to the 4600 valve being designed for single tank system only, set valve type to 1.
K
Press
or
L
Press
to validate the selection and move to the next parameter.

6.5.7. Tank in service (TS)

Caution
This parameter appears only if number of tanks (NT) is set to 2. If it appears, the 4600 valve
being a single tank system, go back to number of tanks (NT) and set it to 1.

6.5.8. Unit capacity (C)

Set the unit capacity.
Note
The unit capacity parameter is only available if the controller type has been programmed for
volumetric regeneration.
Mandatory
Enter the capacity of the media bed in m
displayed in the upper left corner) or in liters for filter (V is displayed in the upper left
corner).
Note
The unit capacity can be set from 0.1 to 9999 x 1000 °TH*m
grains if DF=GAL.
M Press
or
N
Press
to validate the selection and to move the next parameter.
Ref. MKT-IM-028 / A - 03.07.2018
until "---1" is displayed.
to select the unit capacity.
Installer Manual Fleck 4600 SXT - Programming
3
x °TH or g as CaCO
3
, g as CaCO
for softener system (C is
3
equivalent or in
3
53 / 98