System Sizing; Recommendations; Injector/Dlfc/Blfc-Valve Configuration; Sizing A Softener (Single Unit) - Pentair FLECK 4600-SXT Installer Manual

Table of Contents

Advertisement

Installer Manual Fleck 4600 SXT - System sizing
4.

System sizing

4.1.

Recommendations

4.1.1. Injector/DLFC/BLFC-Valve configuration

Diameter
Valve
type
[in]
6
7
8
4600/
1600
9
1650
10
12
13
4.2.

Sizing a softener (single unit)

4.2.1. Parameters to be considered

Whenever installing a softener, it is preferable to have full water analysis to ensure the inlet water
content will not affect the resin bed.
Note
Please consult your resin manufacturer specifications to ensure that no additional
pretreatment prior to softening is required.
24 / 98
Resin
volume
L
DF
Color
5 - 8
0
Red
9 - 14
15 - 21
22 - 28
1
White
29 - 42
43 - 56
2
Blue
57 - 70
Injector
UF
Color
N/A
N/A
Ref. MKT-IM-028 / A - 03.07.2018
DLFC
BLFC
[gpm]
DF [gpm] UF [gpm]
0.8
0.125
1.2
1.5
0.25
2.0
2.4
3.5
0.50
4.0
N/A