Example Of Basic Settings - Bentone B 80i-3R FAME J Installation And Maintenance Instruction

Table of Contents

Advertisement

9.4

Example of Basic settings

Basic settings should only be seen as setting values to get burner to start.
Once the burner has started and established flame, it is necessary to adjust the
settings so that they are adapted to the installation and the fuel used.
B 80i-3R
Burner output:
Estimated nozzle output:
(* Calorfic value Fuel oil
This provides the following nozzle according to the nozzle table, (see Technical
data).
1307 kW distributed over 3 nozzles:
Nozzle, Stage 1:
Nozzle, Stage 2:
Nozzle, Stage 3:
Pump pressure:
Setting values for 1307 kW according to basic setting diagram, (see Technical
data).
Stage 1+2
Insert
Stage 3
P0 Ignition air damper
Air
P1 Low load air damper
P2 ON Solenoid valve 2 open2
P2 d preset air damper
P2 Air damper stage 2
P2 OFF Solenoid valve 2 disconnection
P3 ON Solenoid valve 3 opens
P3 d preset air damper
P3 Air damper stage 3
P3 OFF Solenoid valve 3 disconnection
Selection of output and connection between the different power stages must
be selected and adjusted so that the system achieves good functionality.
92
Bentone
1957 kW
1957 / 11.86*
=
165 kg/h
=
11.86 kWh/kg)
13.50 Gph
703 kW
12.00 Gph
627 kW
12.00 Gph
627 kW
14.0 bar
=
=
=
=
=
=
=
=
=
=
=
=
18
42
18°
18°
35°
53°
53°
35°
65°
80°
80°
65°
165 105 88-3