Installation- and maintenance instruction
STG 146/2
LME11.230C2E
MB-DLE 403
Translation of the original instructions.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the STG 146/2 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bentone STG 146/2

  • Page 1 178 032 26-6 P93783  2022-11-16 Providing sustainable energy solutions worldwide Installation- and maintenance instruction STG 146/2 LME11.230C2E MB-DLE 403 Translation of the original instructions.
  • Page 2 1~230V 1,0A 50Hz IP 20 Motor supply MADE IN SWEDEN BY 1. Manualer på övriga språk 1. Manuals in other languages 1. Manualer på andre sprog 2. www.bentone.com\ 2. www.bentone.com\ 2. www.bentone.com\ nedladdning eller scanna download or scan QR-code. download eller scan QR-koden.
  • Page 3: Table Of Contents

    Startup ................... 21 Control of combustion .............. 21 Technical data ...............6 6.5 Setting the air pressure switch ..........22 Dimensions STG 146/2 ..............6 6.6 Setting the gas pressure switch, min........23 Capacity range ................7 Gas categories, approved gases ..........7 Gas valve MultiBloc DLE 403 ..........24 2.4...
  • Page 4: General Information

    Make sure that the burner is suitable for the application (see Technical • Data). All components must be installed without being bent, twisted or • subjected to mechanical or thermal forces that affect components. 172 515 01-2  2021-10-05 Bentone...
  • Page 5: What To Do If You Smell Gas

    Prevent open fl ames or sparking, e.g. do not turn lights on or off, do • not use any electrical appliances or mobile phones. • Evacuate the building. Notify the installer or gas supplier of the problem so that it can be • rectifi ed. Bentone...
  • Page 6: Technical Data

    Operation in installations according to EN 303 and EN 676. • Fuels: Natural gas H, E, L, LL. • LPG, Butane and Propane. • Dimensions STG 146/2 ø B ø C Flame tube Flame tube Flame tube Length of flame tube...
  • Page 7: Capacity Range

    Gas quantity at Max. connection Min. connection Gas valve min. power max. power pressure pressure MultiBloc mbar mbar STG 146/2 G20  41 - 133 14.1 MBC 120 See data plate. MB-DLE 405 MB-DLE 407 G25  41 - 133 16.4 MBC 120 MB-DLE 405 MB-DLE 407 G30  47 - 144...
  • Page 8: Setting For Nozzle Assembly And Air Damper

    Basic settings should only be seen as setting values to get burner to start. Once the burner has started and established flame, it is necessary to adjust the settings so that they are adapted to the installation and the fuel used. Air settings Nozzle assembly Scale Burner output Bentone...
  • Page 9: Components

    Air damper Transformer Motor Fixing fl ange Fan housing, front Electrical connection Gas valve (MultiBloc) Connection, gas valve Fan housing, rear Air pressure switch Gas pressure switch, min Ionisation electrode Gas nozzle Shielding wall, fan housing Brake plate Fan wheel Bentone...
  • Page 10: Skeleton Diagrams

    Gas pressure switch, mini Gas pressure switch, maxi Main valve Safety valve Valve proving system Air pressure switch Electrical connection Pos. 5b, 7: Components not required according to EN 676. Required over 1200 kW according to EN 676. 172 515 19  2018-01-08 Bentone...
  • Page 11: Installation

    Connection must be done in accordance with the applicable • regulations. • Connection must conform to the wiring diagram. If any electrical connection other than that recommended by Enertech is used, there is a risk of property damage and personal injury. 172 535 09-2 Bentone...
  • Page 12: Electric Equipment

    The cables of the safety system must be separated so that the outgoing signal is not placed in the same cable as the incoming signal. Wiring diagram Brown Blue Green Yellow Gn/Ye Green/Yellow Black Grey White Orange Violet 172 615 05-3  2022-09-15 Bentone...
  • Page 13: Function Lme

    Reset time after lockout < 1 s < 1 s Reaction time on fl ame failure < 1 s < 1 s Min. ionisation current at fl ame 5 µA 5 µA Max. ionisation current 20 µA 20 µA Bentone...
  • Page 14 Pause c:a 3 s Limiting of starting repetitions LME 11... has a function with start repetition if the flame is not created at start or disappears during operation.. LME 11... allows max. three repetitions during continuous starting cycle. Bentone...
  • Page 15 To change to interface mode, press and hold the reset button longer than 3 s. To go back to the normal position, press and hold the reset button longer than 3 s. If the gas burner control is in the alarm position, it is reset by pressing the reset button 0.5...3 s. Bentone...
  • Page 16: Mounting

    Mount the fixing flange and the supplied gasket on the boiler. If new mounting holes must be drilled, use the fixing flange as a template and fasten with M8-M10 screws. Before obtaining access to electrical and fuel line components all supply circuits must be disconnected. 172 515 20-2  2022-09-07 Bentone...
  • Page 17: Gas Nozzle

    Gas nozzle Check that the ignition and ionization electrodes are correctly set before mounting on the boiler. Natural gas, LPG Natural gas Bentone...
  • Page 18: Tightness Control

    If leaks are found during measurement, locate the source using soapy water or leak detection spray. After sealing: check the tightness of the gas fixture again. Check the gas tightness. Bentone...
  • Page 19: Calculation Of Gas Flow

    Natural gas 34.02 Butane 32.25 116.09 Natural gas 29.25 Propane 24.44 88.00 Lower calorific value H at normal conditions 15 °C and 1013 mbar, EN 676. For exact calorific value of the gas, contact the gas distributor. 172 515 27-2 Bentone...
  • Page 20: Settings

    Turn the screw in the desired direction with an allen key. Turn screw to the right to reduce opening. • Turn screw to the left to increase opening. • Nozzle adjustment Air setting 172 535 20-2 Bentone...
  • Page 21: Startup

    Max % CO Gas quality % CO Lambda 1.2 ≈10 Natural gas 3 - 5 11.9 ≈11.5 Propane 3 - 5 13.9 ≈11.5 Butane 3 - 5 14.1 Liquefied ≈11 3 - 5 13.8 petroleum gas Biogas 3 - 5 Bentone...
  • Page 22: Setting The Air Pressure Switch

    Measure and note the lowest air pressure in the entire work area. Set the air pressure switch to about 10-15% lower than the lowest noted pressure. Test run the burner and check the function in the entire work area. Refi t protective cover. Bentone...
  • Page 23: Setting The Gas Pressure Switch, Min

    When the gas pressure switch stops the burner, the measured value must approximately correspond to the setting on the gas pressure switch. Open ball valve. Remove manometer and close measuring socket. Refi t protective cover. Check gas tightness. 172 535 12-2 Bentone...
  • Page 24: Gas Valve Multibloc Dle 403

    Protective cover start load adjustment Hydralic damping Fixing screw Test nipple (inlet pressure) Test nipple (pressure after go-vernor) Test nipple (pressure in inner assembly) Governor Filter Gas pressure switch Solenoid valve 172 515 45-2 Bentone...
  • Page 25 Turn to the right = outlet pressure is increased • Turn to the left = outlet pressure is reduced • Flow adjustment Adjustment of start gas flow Adjustment of governor Bentone...
  • Page 26: Service

    Replacement upon fault detection Gas pressure switch 10 years 250,000 starts Safety blow-off system 10 years Damper motor 500,000 starts Contactor 10 years 500,000 starts The burner and its components must be recycled according to applicable regulations. 172 615 88-2  2022-09-08 Bentone...
  • Page 27: Combustion Device

    Turn on the main power and open the fuel supply. Start burner and check/adjust combustion. Check for leaks in the gas line. When servicing/replacing components that aff ect combustion, fl ue gas analysis and soot test shall be carried out on the installation. 172 615 90-2 Bentone...
  • Page 28: Fan Motor And Fan Wheel

    Turn on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components that aff ect combustion, fl ue gas analysis and soot test shall be carried out on the installation. 172 615 96-2 Bentone...
  • Page 29: Air Intake And Suction Cone

    Turn on the main power and open the fuel supply. Start burner and check/adjust combustion. Check for leaks in the gas line. When servicing/replacing components that aff ect combustion, fl ue gas analysis and soot test shall be carried out on the installation. 172 615 97 Bentone...
  • Page 30: Replacement Of Electrical Components

    Switch on the main power and check the operation of the new component. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 165 105 11-3 Bentone...
  • Page 31: Vibrations

    • Check tightness of fasteners. Check fan wheel for damage and contamination (replace if necessary). • Check motor shaft and bearings. If they are worn, replace the motor. • Use screw to attach the vibration sensor. 172 615 98 Bentone...
  • Page 32: Control Of Flame Monitoring And Ionization Current

    Required current to ensure detection Min. DC 3 µA Possible detection current Max. DC 20 µA Operational indicator lamp flashes green <5 µA DC >5 µA DC Operational indicator lamp shines green 8.8.1 Flame monitoring ionisation 172 615 02-3 Bentone...
  • Page 33 Max. current for flame detection Max. DC 5.5 µA Required current to ensure detection Min. DC 40 µA Possible detection current Max. DC 60 µA Operational indicator lamp flashes green <45 µA DC >45 µA DC Operational indicator lamp shines green Bentone...
  • Page 34: Handing Over Of The Installation

    Instruct the persons in charge of the operation on the service and • maintenance of the installation and what to do should any troubles occur. Inspection and service must be carried out by authorized personnel. • Review and service should be performed by authorised personnel only. 172 615 04-2 Bentone...
  • Page 35: 10. Troubleshooting

    Voltage lower than 185V. Contact an electrician. Ignition electrodes disrupting ionisation current. Adjust ignition electrodes. Re-polarise the transformer. Poor earth connection. Ensure adequate earth connection. Phase and neutral swapped around. Check wiring diagram and change accordingly. 172 615 06  2018-01-10 Bentone...
  • Page 36 Flame at incorrect angle due to combustion head out of Check the combustion head and readjust. position. Condensation build up in boiler and chimney: Raise the flue gas temperature by increasing gas volume Insulate Flue gas temperature too low or gas volume too low. the chimney. Bentone...
  • Page 37: 11. Service- And Inspection Protocol

    11. Service- and inspection protocol Installation Boiler Efficiency kW: Name: Type: Address: Burner Efficiency kW: Type: Installed by: Date: Date gas/h Efficiency Governor Fluegas Ionisation Pressure temp current Fire Chimney room Measure- °C µ A ment Before After mbar mbar Small Flame Large Flame...