Siemens SIPROTEC 7SS523 V3.2 Manual page 80

Distributed busbar/ breaker failure protection
Table of Contents

Advertisement

Configuration
4.5.1.2
Marshalling
Opening the Con-
figuration Matrix
Figure 4-16 Partial view of the Configuration Matrix
Changing the view
64
To marshal information items of the central unit via the Configuration Matrix you must:
Note
Bay units can only be allocated if they have been "instanciated" by the assignment of
library elements (see Chapter 4.3.5, page 55) and by saving the substation chart
Chapter 4.3.9, page 60.
Open the central unit in DIGSI Manager.
In the function selection of the DIGSI Device Configuration right-click the object
Masking I/O (Configuration Matrix). Click Open object in the context menu.
Or double-click the object. Both methods will open the Configuration Matrix.
Maximize the Configuration Matrix
In the toolbar select the option Indications and commands only from the left of
the two drop-down list boxes.
From the right drop-down list box of the toolbar select the option Configured Infor-
mation.
Click View
Expand
Long text on the upper bar of the Configuration Matrix to hide this column.
For a detailed description, please refer to the SIPROTEC System Description /1/, and
to the DIGSI on-line help.
Information of the type Indications and Commands, allocated to one source and /or
destination, are now displayed depending on the selected filter. You will recognize an
allocation by the character in the intersecting cell of an information row and of a source
or destination column. Such characters will be called tags (flags) in the following.
Information items are row-wise comprised to groups. The group is indicated by the
command buttons on the left border of the Configuration Matrix. These command but-
tons are also called group buttons.
All on the menu bar. Double-click the command button
7SS52 V4 Manual
C53000-G1176-C182-1