Siemens SIPROTEC 7SS523 V3.2 Manual page 361

Distributed busbar/ breaker failure protection
Table of Contents

Advertisement

Note
The jumpers settings on the connectors X103 and X104 must always be the same, i.e.
either both on 1-2 or both on 2-3.
Table A-13
Jumper settings (service port) for the D-CPU-module
Connector
RS232
X103
1-2
X104
1-2
X105
1-2
X106
1-2
X107
1-2
X108
1-2
X109
1-2
X110
1-2
X111
2-3
X112
2-3
1) 2-3, switches the terminating resistors on if the device is connected to the beginning or
the end of a RS485 bus line.
1-2, switches he terminating resistors off
Table A-14
Jumper settings (binary inputs) for the D-CPU module
Connector
Binary-
inputs
X20, X21
BI1
X22, X23
BI2
X24, X25
BI3
X26, X27
BI4
X28, X29
BI5
BI6 to BI12 (on module EAZ, Table A-11, page 343)
1) Delivery setting
Jumper
RS485
optical
1)
any
1)
any
2-3
any
2-3
any
2-3
any
2-3
1-2
2-3
any
2-3
any
2-3
2-3
2-3
1-2
24 V
60 V
1-1
2-2
1-1
2-2
1-1
2-2
1-1
2-2
1-1
2-2
7SS52 V4 Manual
C53000-G1176-C182-1
Settings
Central Unit
Jumper
110 V
220V
3-3
4-4
3-3
4-4
3-3
4-4
3-3
4-4
3-3
4-4
1)
345