Siemens SIPROTEC 7SS523 V3.2 Manual page 260

Distributed busbar/ breaker failure protection
Table of Contents

Advertisement

Control During Operation
Check zone
Colour-coded as-
signment
244
To hide the measured value boxes, proceed analogously. With the measured value
boxes hidden, the menu item View → Measured Value Boxes is not checked off and
the
command button is not active.
The setting for the display of the measured value boxes is saved and restored after
the restart of the Plant Visualization.
You can also show or hide the measured value boxes for the differential current and
for the restraint current of the checkzone. The measured values are displayed as per-
centages.
The assignment of the feeders to a busbar is indicated by a certain colour. This means
that the line and the switchgear symbols are in the same colour as the corresponding
busbar.
If a busbar isolator, or a set of two isolators connected to the same feeder but to dif-
ferent busbars, is closed, the colour of the left or upper bus zone has the priority and
takes possession of the right or lower bus zone (preference).
7SS52 V4 Manual
C53000-G1176-C182-1