Siemens SIPROTEC 7SS523 V3.2 Manual page 293

Distributed busbar/ breaker failure protection
Table of Contents

Advertisement

7.4.4
Overcurrent Threshold Tripping
Example
Test setup
Test steps
7.4.5
Breaker Failure Protection
7.4.5.1
Trip Characteristic for Operating Mode "Unbalancing"
Example
Test setup
Figure 7-15 Test setup for the trip characteristic of the breaker failure protection
For two feeders the overcurrent limit shall be checked which is set in parameter
I>TRIP (XX13/CU).
Arrange the test setup as in Chapter 7.4.2, page 271.
To prevent the differential current supervision from blocking the protection during
the test switch it off with the parameter DIFF SUPERV (6306/CU).
Set the differential current thresholds for the busbar-selective measuring system
and for the check zone with the parameters Id> BZ (6102/CU) and Id> CZ
(6104/CU) to 1,0 I/I
Set the overcurrent threshold with the parameter I>TRIP (XX13/CU) for feeder 1
to 2,0 I/I
and for the feeder 2 to 0,0 I/I
n
Set the isolators so that bay 1 and 2 are connected to the same bus zone
Increase the current in feeder 1 slowly with the test equipment. At 1 I
must output a TRIP command, because the overcurrent threshold for this feeder is
set to 0,0 I/I
. Bay unit 1 must output a TRIP command at 2 I
n
The trip characteristic is assumed to be characterized by the parameters
I> BF (XX18/CU) = 0,5 I/I
(6201/CU) = 0,5 for the stabilizing factor.
The test setup is shown in Figure 7-15, page 277.
.
no
.
n
for the differential current threshold STAB FAC:BF
N
C53000-G1176-C182-1
Checks With Secondary Values
.
N
7SS52 V4 Manual
bay unit 2
no
277