Siemens SIPROTEC 7SS523 V3.2 Manual page 380

Distributed busbar/ breaker failure protection
Table of Contents

Advertisement

Appendix
364
Column "Type" (Function Bay Unit): Informationen that belong to the bay units are
of types 195 to 206. In these types up to 256 information numbers can be addressed.
These types are divided into 4 blocks each with 63 information numbers each. The
blocks are assigned to the bay units. The basic type number is given in brackets.
Example:
Bay Unit
No.
1
2
3
4
5
...
8
...
48
The effective information number of each type number can be calculated with the fol-
lowing formula:
x = 63 ∗ (n - 1) + m
Column "Information number": The basic information number is given in brackets.
Note
Only the annuciations subject to general interrogation are reported as ON/OFF to the
IEC 60870-5-103 interface. Indications that are not subject to general interrogation are
only reported as ON.
Information
n
Number m
1
1
...
63
2
1
...
63
3
1
...
63
4
1
...
63
1
1
...
63
...
...
4
1
...
63
...
...
4
1
...
63
Type
Effective Information
Number x
195
1
...
63
195
64
...
126
195
127
...
189
195
190
...
252
196
1
...
63
...
...
196
190
...
252
...
...
206
190
...
252