Siemens SIPROTEC 7SS523 V3.2 Manual page 253

Distributed busbar/ breaker failure protection
Table of Contents

Advertisement

Figure 6-28 Bay units window − Example
Figure 6-29 Bay status window − Example
To put a single bay for the busbar protection out of or into service at the bay unit (PC
linked to central unit or to bay unit) proceed as follows:
Open the corresponding bay unit in DIGSI Manager.
Click Test in the navigation window.
Double-click Test in the function selection. The Tests window opens (Figure 6-21,
page 228).
Click the entry COMMUNICATION WITH CENTRAL UNIT and then click Run....
The window "Test - 4500 COMMUNICATION WITH CENTRAL UNIT" opens (Fig-
ure 6-30, page 238).
Feeder Shutdown and Commissioning
7SS52 V4 Manual
C53000-G1176-C182-1
237