Siemens SIPROTEC 7SS523 V3.2 Manual page 277

Distributed busbar/ breaker failure protection
Table of Contents

Advertisement

Operation with
Ethernet
Access regulation
for Web Monitor
this way several devices can be operated within the system; the existing installation
can be used for central operation of protection devices.
Link through an Ethernet interface. This type of connection requires an EN100 com-
munication module inside the device, and a connection of that module to a local net-
work.
For more information of the basic functionality, the installation and the operating sys-
tem-specific configuration please refer to the Web-Monitor online help provided on the
DIGSI CD.
The Web Monitor access rights are assigned with DIGSI using the Interfaces entry.
For this purpose, Siemens recommends to allow Read authorization; in doing so, neit-
her the event list can be deleted, nor a command output, nor a saved LED reset via
the Web Monitor. The passwod (000000 for read access) can be assigned via DIGSI
under the entry "Passwords". The default setting is 000001 for restricted operation. If
you specify the Full access level, all these operating actions can also be carried out
through the Web Monitor.
Note
The stage No access has no effect yet, i.e. the user has complete access.
Note
The front operator interface has the IP address http://192.168.1.1
The service interface has the IP address http://192.168.2.1
7SS52 V4 Manual
C53000-G1176-C182-1
Commissioning
261

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents