Siemens SIPROTEC 7SS523 V3.2 Manual page 171

Distributed busbar/ breaker failure protection
Table of Contents

Advertisement

5.5.3
Settings for the Central Unit
Addr.
Setting Title
112
Bay status
127
T-BF rel sup
128
T-BF 2chan
6102
Id> BZ
6104
Id> CZ
6109A
Id> BZ - EF
6111A
Id> CZ - EF
ZERO CR SUPERV ON
6312A
6301
ISOL TIME
6302
ISOL Malfunct
6303
ISOL DC FAIL
6304
ISOL ST 1/1
6305
BLOCKING MODE
6306
DIFF SUPERV
6307
T-Idiff SUPERV
6308
Id> SUPERV BZ
6309
Id> SUPERV CZ
6310
DIF SUP mode BZ
DIF SUP mode CZ
6311
CB SUP TIME
6315
Setting Options
out of service
in service
maintenance
0.02 .. 15.00 sec
0.06 .. 1.00 sec
0.20 .. 4.00 I/Ino
0.20 .. 4.00 I/Ino
0.05 .. 4.00 I/Ino
0.05 .. 4.00 I/Ino
OFF
1.00 .. 180.00 sec
alarm only
blocking
block./release
block./acknow.
OLD
ON
OLD
ON
zone/phase
protection
ON
OFF
1.00 .. 10.00 sec
0.05 .. 0.80 I/Ino
0.05 .. 0.80 I/Ino
alarm only
blocking
block./release
alarm only
blocking
block./release
1.00 .. 180.00 sec
Default Setting
in service
Bay status
15.00 sec
Supervision bin. input
BF-release
0.06 sec
Supervision time BF start /
release
1.00 I/Ino
Diff-current threshold - selective
1.00 I/Ino
Diff-current threshold -
check zone
0.25 I/Ino
Diff-current threshold - selective
- EF
0.25 I/Ino
Diff-current threshold - check
zone - EF
Ein
Zero crossing supervision
7.00 sec
Limit value isolator time
alarm only
Reaction on isolator malfunction
Treatment isolator status on
OLD
DC fail
Treatment isolator status not
OLD
plausible
Blocking mode on failure
zone/phase
Differential current supervision
ON
Time delay for diff-current
2.00 sec
supervision
Limit value diff-current
0.10 I/Ino
supervision -BZ
Limit value diff-current
0.10 I/Ino
supervision -CZ
Diff-current supervision
blocking
mode -BZ
Diff-current supervision
alarm only
mode -CZ
7.00 sec
CB supervision time
7SS52 V4 Manual
C53000-G1176-C182-1
Supervisory Functions
Comments
155