Siemens SIPROTEC 7SS523 V3.2 Manual page 211

Distributed busbar/ breaker failure protection
Table of Contents

Advertisement

5.17.2 Setting Notes
T-Annunc.1
T-Annunc.2
T-Annunc.3
T-Annunc.4
5.17.3 Settings of the Bay Unit
Addr.
Parameters
2801
T-Annunc.1
2802
T-Annunc.2
2803
T-Annunc.3
2804
T-Annunc.4
2811
ANNUN1byCU
2812
ANNUN2byCU
2813
ANNUN3byCU
2814
ANNUN4byCU
2821
ANN1Fct.Nr
2822
ANN2Fct.Nr
2823
ANN3Fct.Nr
2824
ANN4Fct.Nr
tion to be generated. So, when the respective user-defined annunciation is displayed
as ON in the bay unit, at the same time it seems as if a binary input to which this binary
input annunciation is configured was activated by a binary signal. Chapter A.10, page
372 gives an overview of the configurable input functions with the corresponding func-
tion numbers (FNo.).
The parameters T-Annunc.1 (2801/BU), T-Annunc.2 (2802/BU),
T-Annunc.3 (2803/BU) and T-Annunc.4 (2804/BU) are used to set the delay
times for the user-defined annunciations 1, 2, 3 and 4.
Setting Options
0.00..10.00 s
0.00..10.00 s
0.00..10.00 s
0.00..10.00 s
NO
YES
NO
YES
NO
YES
NO
YES
0..9999
0..9999
0..9999
0..9999
Default Settings
0.00 s
Delay time for 1st user defined
annunciation
0.00 s
Delay time for 2nd user defined
annunciation
0.00 s
Delay time for 3rd user defined
annunciation
0.00 s
Delay time for 4th user defined
annunciation
NO
Processing of annunciation 1 by
central unit
NO
Processing of annunciation 2 by
central unit
NO
Processing of annunciation 3by
central unit
NO
Processing of annunciation 4 by
central unit
0
Binary input annunciation
(Fct.nr) by annunc.1
0
Binary input annunciation
(Fct.nr) by annunc.2
0
Binary input annunciation
(Fct.nr) by annunc.3
0
Binary input annunciation
(Fct.nr) by annunc.4
7SS52 V4 Manual