Distributed busbar/ breaker failure protection
Table of Contents

Advertisement

5.9.10 List of Information from the Central Unit
FNo.
10471
IsoProhib/Maint
10478
>EF charact.
10486
TripRelErr
10487
>TRIP-Release
176.1135 $01 $02
177.1360 >Trip $03
177.1361 TripBIErr $03
177.1362 noTripRel $03
177.1363 Trip BI $03
5.9.11 Settings for the Bay Unit
Addr.
Setting Title
128
T-BF 2chan
1141
T TRIP
7101
LANGUAGE
5.9.12 List of Information from the Bay Unit
FNo.
1156
>CB test
1174
CB in Test
1181
CB Test Trip
7616
>TRIP release
$00, .., $03 are variables which will be automatically replaced on entry in the event
buffer by
$00 Number of the bay unit
$01 Bay name
$02 Name of the switching element (e.g. isolator or circuit breaker)
$03 Name of the bus zone
Alarm
Setting Options
0.06 .. 1.00 s
0.01..32.00 s
integrated operator control
Alarm
Isolator oper. prohibitted (maintenance)
>Earth fault characteristic active
Timing error trip release
>TRIP-Release for external command
$01 circuit breaker $02
>Trip command for $03
Timing error external Trip command $03
No release of Trip command $03
Trip command by BI for $03
Default Setting
0.06 s
0.15 s
DEUTSCH
ENGLISH
FRANCAIS
ESPANOL
ITALIANO
PYCCK.
>CB test start
Circuit breaker test in progress
Circuit breaker test: General trip
>Trip release
C53000-G1176-C182-1
Protection General
Comments
Comments
Supervision time BF start / re-
lease
Minimum trip command duration
ENGLISH
Comments
7SS52 V4 Manual
173