BURNER CONNECTION TO THE BOILER

REFRACTORY LINING

If a lining is necessary around the combustion head of the burner, it
must comply with the instructions in accordance with the boiler manu-
facturer's instructions.
The refractory lining on the hatch of the combustion chamber protects
the boiler hatch from the high temperatures that develop in the com-
bustion chamber.
It also abbreviates the time necessary to reach the proper temperature,
optimizing combustion.
We recommend using good quality refractory material which can resist
temperatures in excess of 1500°C (42/44% alumina).
Recommendations for correct installation of refractory material:
Refractory material lining should be applied only to boiler door.
Application in other parts of the combustion chamber would redu-
ce the thermal exchange with the outside, causing deterioration of
the boiler combustion chamber.
Application of excess refractory material will also cause a
significant reduction in the volume of the combustion chamber,
preventing optimal combustion due to insufficient volume.
DANGER / ATTENTION
Seal the space between the burner sleeve and the hold on the
refractory material inside the boiler door completely with suitable
material.
A
Combustion head
B
Minimum opening 20 mm on diameter
C
Refractory material
11 / 42
0006160409_202305
ENGLISH
A
B
C