TECHNICAL SPECIFICATIONS

MODEL
Maximum natural gas thermal power
Minimum natural gas thermal power
¹) natural gas emissions
Natural gas operation
Natural gas maximum flow rate
Natural gas minimum flow rate
Natural gas minimum pressure
Natural gas maximum pressure
Diesel fuel maximum flow rate
Diesel fuel minimum flow rate
Maximum diesel fuel thermal power
Minimum diesel fuel thermal power
50hz pump motor
³) diesel emissions
Diesel viscosity
Diesel operation
50hz fan motor
50 hz ignition transformer
50Hz three-phase electrical data
50Hz single-phase electrical data
Protection rating
Control box
Flame detection
operating ambient air temperature
Sound pressure**
Sound power***
Weight with packaging
Weight without packaging
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Lower calorific power:
Diesel fuel: Hi = 11.86 kWh/kg = 42.70 Mj/kg
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations. Measurement accuracy σ = +/- 1.5 dB(A).
*** Acoustic pressure was obtained characterizing the manufacturer's laboratory with a sample source; this measurement has a class 2 accuracy
(engineering class) with a standard deviation of 1.5 dB(A).
ACOUSTIC SHROUD
If it is necessary to reduce the sound pressure level, install a suitable acoustic shroud. (see technical price list and contact the dealer) ).

STANDARD ACCESSORIES

MODEL
Burner coupling flange gasket
Stud bolts
Hexagon nuts
Flat washers
Hoses
Filter
mg/kWh
hPa (mbar)
hPa (mbar)
mg/kWh
6 / 42
0006160409_202305
TBML 2000 ME
kW
20000
kW
2850
Class 2
Electronic modulation
Stm³/h
2116
Stm³/h
302
250
500
kg/h
1686
kg/h
422
kW
20000
kW
5000
kW
7.5
Class 2
6 cst / 20°C - 1,5°E / 20°C
Electronic modulation
kW
45
2x5kV - 30mA - 230V
3L 400V - 90,3A - 55,66kW
1N 230V - 2,2A - 0,505kW
IP54
BT 335
Light sensor
°C
-15 ÷ +40
dBA
80
dBA
96
kg
980
kg
580
TBML 2000 ME
1
N°8 M20
N°8 M20
N°8 Ø20
No.2 - 1" 1/2" x 1500
1" 1/2

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

67550010

Table of Contents