Maintenance - baltur TBML 2000 ME Instruction Manual For Installation, Use And Maintenance

Electronic modulating mixed gas/diesel burner
Table of Contents

Advertisement

Available languages

Available languages

ENGLISH

MAINTENANCE

Analyse combustion gases and check that the emission values are
correct at least once a year, in compliance with current law.
Clean air dampers, the air pressure switch with pressure port and
the relevant pipe, if any.
Check the electrode condition. Replace them, if necessary.
Clean the flame sensor, replace it if necessary.
Have the burner and the chimney cleaned by specialised person-
nel (stove repairer); a clean burner is more efficient, lasts longer
and is quieter.
Check that the fuel filter is clean. Replace it, if necessary.
Check that all components of the combustion head are in good
condition, have not been deformed and are free from impurities
or deposits deriving from the installation environment and/or from
combustion.
Analyse combustion gases and check emissions values.
If the combustion head needs to be cleaned, remove the components
following the procedure indicated below:
remove the flame sensor;
Disconnect the connectors of gas solenoid valves, diesel and gas
servomotor.
unscrew the anchoring screws (12), and open the ventilating
body;
pull out the ignition cables (14) from their electrode terminals (13);
unscrew the screw (8) from the buffer (17)
Pull out the entire mixer unit in the direction shown by the arrow.
When you have finished maintenance work, proceed to reassem-
ble the combustion head, following the same procedure in rever-
se, after checking the correct position of the ignition electrodes.
17
30 / 42
0006160409_202305
8
14
13
8
13
17
14