Electrical Connections - baltur TBML 2000 ME Instruction Manual For Installation, Use And Maintenance

Electronic modulating mixed gas/diesel burner
Table of Contents

Advertisement

Available languages

Available languages

ELECTRICAL CONNECTIONS

It is advisable to make all connections with flexible electric wire.
Conductor cross-sections not specified are to be considered as
0,75 mm².
The power lines must be distanced from the hot parts.
The burner can be installed exclusively in environments with
pollution degree 2 as specified in Standard EN 60204-1.
Make sure that the power line frequency and voltage values
comply with those mentioned in the plate.
The three-phase or single-phase power supply line must have a
circuit breaker with fuses.
The regulations further require a switch on the burner power
supply line, to be positioned outside the boiler room and easily
accessible.
The main line and relevant switch with fuses must be suitable to
support the maximum current absorbed by the burner.
A single-pole switch with a contact opening gap equal or above
3 mm is required for the mains supply connection, in accordance
with current safety regulations.
Refer to the wiring diagram for electrical connections (line and
thermostats).
Strip the outer insulation of the power cable just as necessary for
the connection, preventing the cable to touch metal parts, and
provide a longer length for the earth conductor.
CAUTION / WARNINGS
Only professionally qualified personnel may open the burner
electrical switchboard.
15 / 42
0006160409_202305
ENGLISH