Connection

For B12C operation, the AC inputs of the two units are powered by the outputs of
a transformer with a Dy5d6 vector group. The master unit must be connected to the
secondary star output of the transformer. The slave unit must be connected to the
secondary delta output of the transformer.
Example vector group
Figure 5‑9. B12C vector group
For B18C operation, the AC inputs to the three units are powered by the outputs
of a transformer with a Dd0 d0+20° d0−20° vector group. The master unit must
be connected to the secondary delta 0° output of the transformer. The first slave
unit must be connected to the secondary delta 0+20° output of the transformer. The
second slave unit must be connected to the secondary delta 0−20° output of the
transformer.
Example vector group
Figure 5‑10. B18C vector group
57010241-00B
Phase shift from primary to secondary
Phase shift from primary to secondary
Phase position of L1 for the different secondary systems
Phase shift from primary to secondary
Phase position of L1 for the different secondary systems
Installation, Setup, and Operation
®
Thyro‑PX
DC Power Controller
Primary
Secondary 150°
Secondary 180°
Phase shift from primary to secondary
Phase shift from primary to secondary
Primary
Secondary 0°
Secondary +20°
Secondary -20°
5‑17