Table 6‑1. Using LED states for troubleshooting
Troubleshooting
Check
Is the green ON/
READY LED lit?
Is the red ON/
READY LED lit?
Is the red ON/
READY LED
blinking?
Is the orange ON/
READY LED
blinking?
Is the red LIMIT
LED lit?
Is the FAULT LED
lit?
Are any red
CONTROL LEDs
lit?

AE GLOBAL SERVICES

Please contact AE Global Services if you have questions or problems, or if you need
customer support. Before contacting AE Global Services, please work through the
provided troubleshooting. When you contact Global Services, please include the unit
serial number and part number. These numbers are available on unit labels.
 Important
For returns and repairs, please contact AE Global Services to get the correct
shipping address.
57010241-00B
If no: The auxiliary 230 VAC or 24 VDC supply is faulty.
If yes: There is an EEPROM fault.
If yes: The hardware configuration is incorrect.
If yes: The firmware is being updated.
If yes: The unit is unable to supply enough power to match
the setpoint due to a limiting condition. When an internal
protection limit is exceeded, the output is limited but not shut
off.
1. Disable the output.
2. Verify that the limitation setting is correct.
3. Verify that the unit load and load connections are correct.
If yes: The unit has detected a fault. This fault will generate
error data that can be viewed using the Thyro‑Touch display
or the Thyro-Tool Pro software.
If yes: The unit has a fault in the corresponding power section.
Troubleshooting and Global Services
®
Thyro‑PX
DC Power Controller
Action
6‑2