Table 3‑6. Fan current, air volume, and sound pressure (Continued)
Model
Fans for HF units must be running when the unit is operating. Connect the fans according
to connecting diagrams. When operating conditions are below +10°C (+50°F), a longer fan
startup time is required. Therefore, the overcurrent protection device should be rated at twice
the specified continuous current.

ENVIRONMENTAL SPECIFICATIONS

The two following tables describe the environmental specifications for the Thyro-
PX DC unit.
Table 3‑7. Environmental standard specifications
Description
Overvoltage
Pollution degree
Table 3‑8. Climatic specifications
Operating
Storage
57010241-00B
Current (A)
50 Hz
60 Hz
Temperature
Self cooled models:
+0°C to +45°C
+32°F to +113°F
Force cooled models:
+0°C to +35°C
+32°F to +95°F
–25°C to +55°C
–13°F to +131°F
Specifications
Thyro‑PX
Air Volume
3
(m
/h)
Specification
Category III per IEC 62477-1
2
Relative Humidity
[1]
5% to 85%
3
3
1 g/m
to 25 g/m
3
3
1 g/m
to 25 g/m
5% to 95%
3
3
1 g/m
to 29 g/m
®
DC Power Controller
Sound Pressure
(dbA @ 1 m)
Air Pressure
89.9 kPa to 106 kPa
899 mbar to
1060 mbar
Equivalent altitude:
+1000 m to –500 m
[2]
(+3281' to –1640')
78.8 kPa to 106 kPa
788 mbar to
1060 mbar
Equivalent altitude:
+2000 m to –500 m
(+6562' to –1640')
3‑5