PROGRAMMING
INSTALLER/DEALER SETTINGS
Setting
Loss of Cell Signal Timeout
Light Reporting (PowerG)
Temperature Reporting (PowerG)
SIA Limits
NOTE: For UL resi burg set entry delay to 45 sec
and exit delay to max 120 sec. For UL Commercial
Burg (UL2610) maximum entry and exit delay
should not exceed 60 sec.
NOTE: For ULC Security Level I (resi burg) set entry
delay to 180 sec. For ULC Security Level II
(commercial burg) set entry delay to 60 sec and
exit delay to 45 sec max.
NOTE: For EN Grade 2 installations set Entry Delay
to 45 sec and Exit Delay to 30 sec.
Default
Select the length in minutes (10-120) before reporting a loss in cellular signal.
30
NOTE: For UL Commercial Burg (UL2610) the cell supervision is hardcoded to 200s
When Enabled, PowerG devices that support light sensor capabilities report light status
Disabled
to the Panel. Data is stored for future use.
When Enabled, PowerG devices that support temperature measurement, report
Disabled
temperature information to the Panel. Data is stored for future use.
General Internal
When enabled, the range for entry and exit delays is as follows:
-Entry delay: 30-240 seconds, Exit Delay: 45-254 seconds
When disabled, the range for entry and exit delays are as follows:
Enabled
-Entry delay: 5 to 240 seconds, Exit delay: 5 to 254 seconds
When enabled the range for Dialer Delay is: 15 to 45 seconds
When disabled the range for Dialer Delay is: 0 to 254 seconds
QOLSYS CONFIDENTIAL AND PROPRIETARY
PAGE
71
OF
Description
158