Combustible Mantels - Regency Fireplace Products Panorama P33CE Series Owners & Installation Manual

Zero clearance direct vent gas fireplace
Table of Contents

Advertisement

COMBUSTIBLE MANTELS

Because of the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of unit are shown in the
diagram below.
Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible board.
This drawing is to scale at 1:6 (one inch = 6 inches). Mantel can be installed anywhere in shaded area or higher using the above scale.
Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour.
Combustible mantel leg clearances as per diagrams below:
Mantel Clearances
12
10
8
12" (305mm)
16
14
12
10
15-3/4" (400mm)
8
6
13-3/4"(349mm)
4
2
0
24-1/4"(616mm)
to floor
6
4
2
Drywall
7-1/2"(191mm)
0" - 3-1/2" (89mm)
Non-combustible material
11-3/4"(298mm)
Top opening
of Unit
3"(76mm)
Standoff
Side View
installation
P33CE-10 Direct Vent Gas Fireplace
|
11
|
11