Installation And Application Information - Daikin Clima-Flex CLIC STAND ALONE Series Installation, Operation And Maintenance Manual

Air-cooled scroll compressor chiller water generator unit
Table of Contents

Advertisement

OPERATING AND STANDBY LIMITS
Table 1. Table unit CLIC
Maximum standby ambient temperature
Maximum operating ambient temperature
Minimum operating ambient temperature (standard control)
Outgoing chilled water temperature
Outgoing chilled fluid temperatures (with antifreeze) - Note that in cases of high ambient tempera-
ture, the lowest outgoing water temperature settings may be outside the chiller's operating enve-
lope; see the chiller's operating envelope. Outgoing water temperature settings may be outside the
chiller's operating envelope; refer to the Clima Flex Tools to make sure that the chiller is capable
of the required elevation.
Maximum evaporator inlet fluid temperature
Maximum non-operating evaporator inlet fluid temperature
NAMEPLATES
The unit nameplate is located on the outside of the unit power
panel. Both the model number and serial number are located on
the unit nameplates; the serial number is unique to the unit.
These numbers should be used to identify the unit in case of
service, parts or warranty questions. This nameplate also
contains the unit's refrigerant charge and electrical ratings. The
evaporator nameplate is under the insulation and contains the
serial number. The compressor nameplate is located on each
compressor and provides pertinent electrical information.
!
WARNING
Installation should be performed by qualified personnel who
are familiar with local codes and regulations.
INSPECTION
Check all items carefully against the bill of lading. Inspect all
units for damage upon arrival. Report shipping damage and file a
claim with the carrier. Check the unit nameplate before unloading,
making sure it matches the available power supply.
Clima Flex is not responsible for physical damage that occurs
after the unit leaves the factory.
HANDLING
Take care to avoid rough handling of the unit. Do not push or pull
the unit from other than the base while seated on properly sized
dollies.
To lift the unit, 2-1/2 (64 mm) diameter lifting eyes are provided
at the base of the unit. Arrange the spreader bars and cables to
prevent damage to the condenser coils or cabinet (see Figure 1).
!
CAUTION
All lifting locations must be used to avoid damage to the unit.
iom-clicsa-cf-eng

Installation and Application Information

!
!
8
!
DANGER
Improper rigging, lifting or moving of a unit can result in
property damage, serious personal injury or death. Follow
the rigging and moving instructions carefully. Do not stand
under the unit while it is being lifted or installed.
Figure 1. Required elevation arrangement.
PLACEMENT OF THE UNIT
CLIC STAND ALONE series units are for outdoor applications and
can be mounted on the roof or on the ground. For roof mounted
applications, install the unit on a steel channel or I-beam frame to
support the unit above the roof.
130°F (54°C)
105°F (41°C)
32°F(0°)
40°F to 65°F (4°C to 18°C)
15°F to 65°F (-9°C to
18°C)
81°F (27°C)
100°F (38°C)
!
www.clima-flex.com