Daikin Clima-Flex CLIC STAND ALONE Series Installation, Operation And Maintenance Manual page 40

Air-cooled scroll compressor chiller water generator unit
Table of Contents

Advertisement

Index Size Acronym
211
2
PwrRunCircs_Perc
213
2
AFC2
215
2
AFE1
217
2
AFC1
219
1
IOprbCfgWrn
220
2
W_UsrTempRegPID
226
1
DfrStatus_Circ1
227
2
AIN_PwrReq_Circ1
231
1
SWverEXP
232
1
SWverMAIN
233
1
PWRP_ErrCode_Circ1 UDINT
234
1
PWRP_ErrCode_Circ2 UDINT
Input Status
Index Size Acronym
0
1
A01
1
1
A02
2
1
A03
3
1
A04
4
1
A05
5
1
A06
6
1
A07
7
1
A08
8
1
A09
9
1
A10
10
1
A11
11
1
A12
12
1
A13
13
1
A14
14
1
A15
15
1
A16
16
1
A17
17
1
A18
18
1
A19
19
1
A20
20
1
A21
21
1
A22
22
1
A23
23
1
A24
24
1
A25
25
1
A26
26
1
A27
27
1
A28
28
1
A29
29
1
A30
30
1
A31
31
1
A32
32
1
A33
33
1
A34
34
1
A35
35
1
A36
36
1
A37
37
1
A38
38
1
A39
39
1
A40
40
1
A41
41
1
A42
42
1
A43
43
1
A44
44
1
A45
45
1
A46
46
1
A47
47
1
A48
48
1
A49
49
1
A50
50
1
A51
iom-clicsa-cf-eng
Min
Max
DataType
R/W
Value
Value
REAL
R
REAL
R
REAL
R
REAL
R
UINT
R
REAL
R
UINT
REAL
R
UINT
R
UINT
R
-
-
R
-
-
R
Min
Max
DataType
R/W InitValue UoM
Value
Value
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
BOOL
R
Init
UoM
Description
Value
0
PERCENT
PwrRunCircs_Perc - Circuit capacity percentage by
compressors ON
0
CELSIUS
AFC2 - Cond.2 frost temp
0
CELSIUS
AFE1 - Evap.1 frost temp.
0
CELSIUS
AFC1 - Cond.1 frost temp
0
IOcfgPrbWrn - I/O probe confi guration warnings
0
CELSIUS
W_UsrTempRegPID - Water temperature value used
by control
Defrost status of circ 1
0
PERCENT
Capacity request using analogue input on circuit 1
0
Firmware B version on expansion board
0
Firmware B version on main board
-
-
Power+ circuit 1 error code
-
-
Power+ circuit 2 error code
Description
FALSE
Unit - Error in the number of retain memory writes
FALSE
Unit - Error in retain memory writes
FALSE
Unit - Remote alarm by digital input
FALSE
Unit - Remote set point out of range alarm
FALSE
Unit - User return water temperature probe broken or
disconnected alarm
FALSE
Unit - User delivery water temperature probe broken or
disconnected alarm
FALSE
Unit - Tank temperature probe broken or disconnected alarm
FALSE
Unit - User pump 1 overload
FALSE
Unit - User pump 2 overload
FALSE
Unit - Flow switch alarm, no fl ow present with user pump 1
active
FALSE
Unit - Flow switch alarm, no fl ow present with user pump 2
active
FALSE
Unit - User pump group alarm
FALSE
Unit - User 1 pump maintenance
FALSE
Unit - User 2 pump maintenance
FALSE
Unit - High chilled water temperature
FALSE
Unit - Source return water/air temperature probe broken or
disconnected alarm
FALSE
Unit - Source 1 pump maintenance
FALSE
Unit - Free cooling fault
FALSE
Circuit 1 - Discharge pressure probe broken or disconnected
alarm
FALSE
Circuit 1 - Condensing temperature probe broken or discon-
nected alarm
FALSE
Circuit 1 - Suction pressure probe broken or disconnected
alarm
FALSE
Circuit 1 - Evaporation temperature probe broken or discon-
nected alarm
FALSE
Circuit 1 - Discharge temperature probe broken or discon-
nected alarm
FALSE
Circuit 1 - Suction temperature probe broken or disconnect-
ed alarm
FALSE
Circuit 1 - High pressure alarm from pressure switch
FALSE
Circuit 1 - High pressure alarm from transducer
FALSE
Circuit 1 - Low pressure alarm from transducer
FALSE
Circuit 1 or unit - Frost evaporation temperature alarm
FALSE
Circuit 1 - Low pressure alarm from pressure switch
FALSE
Circuit 1 - Overload compressor 1
FALSE
Circuit 1 - Overload compressor 2
FALSE
Circuit 1 - Compressor 1 maintenance
FALSE
Circuit 1 - Compressor 2 maintenance
FALSE
Circuit 1 - Source fan 1 maintenance
FALSE
Circuit 1 EVD - Low superheat (SH)
FALSE
Circuit 1 EVD - Low evaporation pressure (LOP)
FALSE
Circuit 1 EVD - Maximum evaporating pressure (MOP)
FALSE
Circuit 1 EVD - Valve motor error
FALSE
Circuit 1 EVD - Emergency closing
FALSE
Circuit 1 EVD - Incomplete valve closing
FALSE
Circuit 1 EVD - Offl ine
FALSE
Circuit 1 Envelope - General alarm + Zone alarm
FALSE
Circuit 1 BLDC - Delta pressure greater than the allowable
at startup
FALSE
Circuit 1 BLDC - Starting failure
FALSE
Circuit 1 BLDC - Low diff erential pressure
FALSE
Circuit 1 BLDC - High discharge gas temperature
FALSE
Circuit 1 Inverter - Offl ine
FALSE
Circuit 1 Inverter - General alarm + Error code
FALSE
Unit - Secondary board is offl ine
FALSE
Unit - Error in the number of retain memory writes on
Secondary board
FALSE
Unit - Error in retain memory writes on Secondary board
40
Mapping Table
www.clima-flex.com