Daikin Clima-Flex CLIC STAND ALONE Series Installation, Operation And Maintenance Manual page 36

Air-cooled scroll compressor chiller water generator unit
Table of Contents

Advertisement

Index Size Acronym
DataType
276
1
Hc82
USINT(0..2)
277
1
AI_CfgLim-
USINT
Max_Grp3
278
1
S056
UINT(20..999)
279
2
S057
REAL
281
2
S058
REAL
283
1
S059
UINT(0..999)
284
2
S060
REAL
286
1
Hc00
USINT
287
1
AI_CfgLim-
USINT
Max_Grp3_Slv
288
1
Hc03
USINT
289
1
Hc04
USINT
290
1
Hc05
USINT
291
1
Hc06
USINT
292
1
Hc07
USINT
293
1
Hc08
USINT
294
1
Hc09
USINT
295
1
Hc10
USINT
296
1
Hc11
USINT
297
1
Hc14
USINT
298
1
Hc15
USINT
iom-clicsa-cf-eng
Min
Max
Init
R/W
UoM
Value
Value
Value
R/W 1
R/W 9
R/W 20
SECOND
R/W -0.8
CELSIUS
R/W 30
DELTAKEL-
VIN
R/W 30
SECOND
R/W 0
DELTAKEL-
VIN
0
4
R/W 1
R/W 11
0
2
R/W 0
0
1
R/W 0
0
1
R/W 0
0
6
R/W 1
0
6
R/W 5
0
6
R/W 4
0
5
R/W 0
0
5
R/W 0
0
5
R/W 0
R/W 1
R/W 2
36
Description
Hc82 - Analogue output 2 secondary confi g. (0= Not used,
1=Source fan on/off , 2=Source fan mod)
AI_CfgLimMax_Grp3 - Lim max probe group 3
S056 - Duration of smart start function
S057 - Source frost alarm threshold
S058 - Source frost alarm diff erential
S059 - Source frost alarm delay time at 1K below threshold
S060 - Source external air temperature off set
Hc00 - Analogue input 3 confi g. (0= Not used, 1= Source
water delivery temp., 2= Outside temp., 3= Discharge temp.,
4= Condensing temp., 5= Suction temp., 6= Evaporation
temp., 7= Return water temp. from user, 8= Delivery water
temp. to user)
AI_CfgLimMax_Grp3 - Lim max probe group 3 secondary
Hc03 - Analogue input 6 confi g. (0= Not used, 1= Source
water delivery temp., 2= Outside temp.,3= Remote set point,
4= Discharge temp., 5= Condensing. temp., 6= Suction temp.,
7= Evaporation temp., 8= Condensing press., 9= Evaporating
press., 10= Return water temp. from user, 11= Delivery water
temp. to user, 12= Capacity request from AIN)
Hc04 - Analogue input 7 confi g. (0= Not used, 1= Source
water delivery temp., 2= Outside temp., 3= Discharge temp.,
4= Condensing temp., 5= Suction temp., 6= Evaporation
temp., 7= Return water temp. from user, 8= Delivery water
temp. to user)
Hc05 - Analogue input 6 confi g. on Secondary board (0= Not
used, 1= Source water delivery temp., 2= Outside temp., 3=
Remote set point, 4= Discharge temp., 5= Condensing. temp.,
6= Suction temp., 7= Evaporation temp., 8= Condensing
press., 9= Evaporating press., 10= Common delivery temp.,
11= Delivery water evap.2 temp., 12= Capacity request from
AIN)
Hc06 - Digital input 4 confi g. (0=Not used, 1=User fl ow
switch, 2=Comp.1 circ.1 overload, 3=Comp.2 circ.1 overload,
4=Remote ON/OFF, 5=Cool/Heat, 6=2nd set point, 7=Re-
mote alarm, 8=User pump 1 overload, 9=LP pressure switch,
10=User pump 2 overload, 11=Remote cmd 1, 12=Remote
cmd 2, 13=Source alarm)
Hc07 - Digital input 5 confi g. (0=Not used, 1=User fl ow
switch, 2=Comp.1 circ.1 overload, 3=Comp.2 circ.1 overload,
4=Remote ON/OFF, 5=Cool/Heat, 6=2nd set point, 7=Re-
mote alarm, 8=User pump 1 overload, 9=LP pressure switch,
10=User pump 2 overload, 11=Remote cmd 1, 12=Remote
cmd 2, 13=Source alarm)
Hc08 - Digital input 6 confi g. (0=Not used, 1=User fl ow
switch, 2=Comp.1 circ.1 overload, 3=Comp.2 circ.1 overload,
4=Remote ON/OFF, 5=Cool/Heat, 6=2nd set point, 7=Re-
mote alarm, 8=User pump 1 overload, 9=LP pressure switch,
10=User pump 2 overload, 11=Remote cmd 1, 12=Remote
cmd 2, 13=Source alarm)
Hc09 - Digital input 4 confi g. on Secondary board (0=Not
used, 1=User fl ow switch, 2=Comp.1 circ.2 overload,
3=Comp.2 circ.2 overload, 4=Remote ON/OFF, 5=Cool/Heat,
6=2nd set point, 7=Remote alarm, 8=User pump 1 overload,
9=LP pressure switch, 10=User pump 2 overload, 11=Remote
cmd 3, 12=Remote cmd 4, 13=Source alarm)
Hc10 - Digital input 5 confi g. on Secondary board (0=Not
used, 1=User fl ow switch, 2=Comp.1 circ.2 overload,
3=Comp.2 circ.2 overload, 4=Remote ON/OFF, 5=Cool/Heat,
6=2nd set point, 7=Remote alarm, 8=User pump 1 overload,
9=LP pressure switch, 10=User pump 2 overload, 11=Remote
cmd 3, 12=Remote cmd 4, 13=Source alarm)
Hc11 - Digital input 6 confi g. on Secondary board (0=Not
used, 1=User fl ow switch, 2=Comp.1 circ.2 overload,
3=Comp.2 circ.2 overload, 4=Remote ON/OFF, 5=Cool/Heat,
6=2nd set point, 7=Remote alarm, 8=User pump 1 overload,
9=LP pressure switch, 10=User pump 2 overload, 11=Remote
cmd 3, 12=Remote cmd 4, 13=Source alarm)
Hc14 - Digital input 1 confi g. (0=Not used, 1=User fl ow
switch, 2=Comp.1 circ.1 overload, 3=Comp.2 circ.1 overload,
4=Remote ON/OFF, 5=Cool/Heat, 6=2nd set point, 7=Re-
mote alarm, 8=User pump 1 overload, 9=LP pressure switch,
10=User pump 2 overload, 11=Remote cmd 1, 12=Remote
cmd 2, 13=Source alarm)
Hc15 - Digital input 2 confi g. (0=Not used, 1=User fl ow
switch, 2=Comp.1 circ.1 overload, 3=Comp.2 circ.1 overload,
4=Remote ON/OFF, 5=Cool/Heat, 6=2nd set point, 7=Re-
mote alarm, 8=User pump 1 overload, 9=LP pressure switch,
10=User pump 2 overload, 11=Remote cmd 1, 12=Remote
cmd 2, 13=Source alarm)
Mapping Table
www.clima-flex.com

Advertisement

Table of Contents
loading

Table of Contents