Installation And Application Information - Daikin Clima-Flex IOM CLIM Series Installation, Operation And Maintenance Manual

Air-cooled fixed compressor chiller water generator unit
Table of Contents

Advertisement

Table 1.
Operating and Standby Limits
Maximum standby ambient temperature
Maximum operating ambient temperature
Minimum operating ambient temperature (standard control)
Cold water outlet temperature
Outgoing chilled fluid temperatures (with antifreeze) - Note that in cases of high ambient temperature,
the lowest outgoing water temperature settings may be outside the chiller operating envelope.
Maximum evaporator inlet fluid temperature
Maximum temperature of inlet fluid to non-operating evaporator
NAMEPLATES
The unit nameplate is located on the outside of the unit power
panel. Both the model number and serial number are located on
the unit nameplates; the serial number is unique to the unit.
These numbers should be used to identify the unit in case of
service, parts or warranty questions. This nameplate also contains
the unit's refrigerant charge and electrical ratings. The evaporator
nameplate is under the insulation and contains the serial number.
The compressor nameplate is located on each compressor and
provides pertinent electrical information.
!
WARNING
Installation should be performed by qualified personnel who
are familiar with local codes and regulations.
INSPECTION
Check all items carefully against the bill of lading.
Inspect all units for damage upon arrival. Report shipping damage
and file a claim with the carrier.
Check the nameplate on the unit before unloading, making sure it
matches the available power supply.
Clima Flex is not responsible for physical damage that occurs
after the unit leaves the factory.
HANDLIING
Take care to avoid rough handling of the unit. Do not push or pull
the unit from other than the base while seated on properly sized
dollies.
To lift the unit, 2-1/2 (64 mm) diameter lifting eyes are provided
at the base of the unit. Arrange the spreader bars and cables to
prevent damage to the condenser coils or cabinet (see Figure 1).
!
CAUTION
All lifting locations must be used to avoid damage to the unit.
iom-clim-cf-eng

Installation and Application Information

!
!
6
!
DANGER
Improper rigging, lifting or moving of a unit can result
in property damage, serious personal injury or death.
Follow the rigging and moving instructions carefully. Do
not stand under the unit while it is being lifted or installed.
Figure 1. Required elevation arrangement.
PLACEMENT OF THE UNIT
The units must be installed in accordance with all national and
local safety standards. If there are no applicable local standards,
the installation must be carried out in accordance with national
standards.
130°F (54°C)
105°F (41°C)
32°F(0°)
40°F A 65°F (4°C to 18°C)
15°F A 65°F (-9°C to 18°C)
81°F (27°C)
100°F (38°C)
!
www.clima-flex.com