Daikin Clima-Flex CLIC STAND ALONE Series Installation, Operation And Maintenance Manual page 35

Air-cooled scroll compressor chiller water generator unit
Table of Contents

Advertisement

Mapping Table
Index Size Acronym
DataType
165
1
C015
UINT(5..999)
166
1
C016
UINT(5..999)
167
1
S021
UINT
168
1
C020
UINT(5..999)
169
1
C021
USINT(0..1)
170
2
C022
REAL
172
2
C023
REAL
174
2
C024
REAL
176
2
C025
REAL
178
2
C026
REAL
180
2
C027
REAL
182
2
C028
REAL
184
2
C029
REAL
186
2
C030
REAL
188
2
C031
REAL
190
2
C032
REAL
192
2
C033
REAL
194
1
C037
USINT(0..1)
195
2
C038
REAL
197
2
C039
REAL
199
1
C040
USINT(0..1)
200
2
C041
REAL
202
2
C042
REAL
204
1
C043
USINT(0..1)
206
1
C046
USINT(1..2)
207
1
C047
USINT
208
1
C048
USINT(1..2)
209
1
S000
UINT(0..999)
210
1
S002
UINT(0..2)
212
1
S022
UINT
213
1
S072
USINT(0..2)
214
1
S008
UINT(0..999)
215
1
S010
USINT(0..2)
216
1
S011
USINT(0..101)
217
1
S012
UINT(0..999)
218
1
S014
USINT(0..2)
219
1
S015
USINT(0..101)
220
2
S016
REAL
222
2
S017
REAL
224
2
S018
REAL
226
1
S019
UINT(0..300)
229
2
Sprb
REAL
231
2
S025
REAL
233
1
S026
UINT(0..999)
234
1
S027
UINT(0..999)
235
2
S028
REAL
237
2
S029
REAL
239
1
U081
USINT(0..7)
240
1
Hc71
USINT(0..3)
241
2
S031
REAL
243
1
S032
UINT(0..999)
244
1
Hc81
USINT(0..2)
245
1
Hc72
USINT(0..3)
246
2
S034
REAL
248
2
S035
REAL
250
2
S036
REAL
252
2
S037
REAL
254
2
S039
REAL
256
2
S040
REAL
258
1
S041
UINT(0..999)
259
2
S042
REAL
261
1
S044
UINT(0..999)
262
1
S045
UINT(0..999)
263
1
S046
UINT(0..99)
264
1
S047
UINT(0..99)
265
1
S048
UINT(0..999)
266
1
S049
UINT(0..999)
267
1
S050
UINT(0..999)
268
1
C049
UINT(0..999)
269
1
C050
UINT(0..999)
270
1
F024
USINT
271
1
F025
USINT
272
1
S053
USINT(0..2)
274
2
S054
REAL
www.clima-flex.com
Min
Max
Init
R/W
UoM
Value
Value
Value
R/W 30
SECOND
R/W 10
SECOND
R/W 0
HOUR
R/W 720
MINUTE
R/W 0
R/W 0
DELTAKELVIN C022 - Discharge temp. probe off set for circ.1
R/W 0
DELTAKELVIN C023 - Suction temp. probe off set for circ.1
R/W 0
DELTAKELVIN C024 - Discharge temp. probe off set for circ.2
R/W 0
DELTAKELVIN C025 - Suction temp. probe off set for circ.2
R/W 0
BAR
R/W 0
BAR
R/W 0
DELTAKELVIN C028 - Cond. temp. probe off set for circ.1
R/W 0
DELTAKELVIN C029 - Evap. temp. probe off set for circ.1
R/W 0
BAR
R/W 0
BAR
R/W 0
DELTAKELVIN C032 - Cond. temp. probe off set for circ.2
R/W 0
DELTAKELVIN C033 - Evap. temp. probe off set for circ.2
R/W 0
R/W 0
BAR
R/W 17.3
BAR
R/W 0
R/W 0
BAR
R/W 45
BAR
R/W 1
R/W 1
2
3
R/W 2
R/W 1
R/W 99
HOUR
R/W 0
R/W 0
MINUTE
R/W 0
R/W 99
HOUR
R/W 0
R/W 0
PERCENT
R/W 0
HOUR
R/W 0
R/W 0
PERCENT
R/W -5
CELSIUS
R/W 10
PERCENT
R/W 50
PERCENT
R/W 5
SECOND
R
0
CELSIUS
R/W 45
CELSIUS
R/W 30
SECOND
R/W 10
SECOND
R/W 30
CELSIUS
R/W 10
CELSIUS
R/W 0
R/W 1
R/W 45
CELSIUS
R/W 240
SECOND
R/W 1
R/W 1
R/W 15
DELTAKELVIN S034 - Source device cool diff erential
R/W 5
DELTAKELVIN S035 - Source device heat diff erential
R/W 20
PERCENT
R/W 80
PERCENT
R/W -1
CELSIUS
R/W 1
CELSIUS
R/W 30
MINUTE
R/W 52
CELSIUS
R/W 20
SECOND
R/W 30
SECOND
R/W 1
MINUTE
R/W 5
MINUTE
R/W 90
SECOND
R/W 30
SECOND
R/W 20
MINUTE
R/W 90
SECOND
R/W 15
SECOND
R/W 0
R/W 0
R/W 0
R/W 3
BAR
35
Description
C015 - Comp. load up time
C016 - Comp. load down time
Time band hours
C020 - Circuit destabilisation max time with one or more
comp. OFF
C021 - Circuit capacity distribution (0=Equalised, 1=Grouped)
C026 - Discharge press. probe off set for circ.1
C027 - Suction press. probe off set for circ.1
C030 - Discharge press. probe off set for circ.2
C031 - Suction press. probe off set for circ.2
C037 - Suction press. probe type (0=0..5V, 1=4..20mA)
C038 - Suction press. probe min value
C039 - Suction press. probe max value
C040 - Discharge press. probe type (0=0..5V, 1=4..20mA)
C041 - Discharge press. probe min value
C042 - Discharge press. probe max value
C043 - Discharge temp. probe type (0=NTC, 1=NTC-HT)
C046 - Number of circuit in the unit
C047 - Type of compressors used (0=1 ON/OFF, 1=2 ON/OFF,
2=BLDC, 3=BLDC + ON/OFF)
C048 - Compressor rotation type (1=FIFO, 2=TIME)
S000 - Source pump 1 maintenance hour threshold (x100)
S002 - Source pump 1 manual mode (0=AUTO, 1=OFF, 2=ON)
Time band minutes
S072 - Source pump activation (0=always on, 1=on with
compressor, 2=modulate on discharge)
S008 - Source fan 1 circ.1 maintenance hour threshold (x100)
S010 - Source fan ON/OFFcirc.1 manual mode (0=AUTO,
1=OFF, 2=ON)
S011 - Source fan inverter circ.1 manual mode (0=AUTO,
1=0%, 2=1%, .. 101=100%)
S012 - Source fan 1 circ.2 maintenance hour threshold (x100)
S014 - Source fan ON/OFF circ.2 manual mode (0=AUTO,
1=OFF, 2=ON)
S015 - Source fan inverter circ.2 manual mode (0=AUTO,
1=0%, 2=1%, .. 101=100%)
S016 - Source fan temp. threshold for cold climates
S017 - Source fan min speed for cold climates
S018 - Source fan speed up speed for cold climates
S019 - Source fan speed up time for cold climates
SPrb - Source external air temperature
S025 - Low noise source fan set point in cooling
S026 - Comp. ON delay after source pump ON
S027 - Source pump delay OFF from comp. OFF
S028 - Source device cool set point
S029 - Source device heat set point
U081 - Pressure alarm reset confi guration
Hc71 - Analogue output 1 confi g. (0= Not used, 1=Source
pump - Source fan on/off , 2=Source fan mod, 3=Free cooling
valve)
S031 - Source fan cool set point at startup
S032 - Source fan cool startup delay
Hc81 - Analogue output 1 secondary confi g. (0= Not used,
1=Source fan on/off , 2=Source fan mod)
Hc72 - Analogue output 2 confi g. (0= Not used, 1=Source pump -
Source fan on/off , 2=Source fan mod, 3=Free cooling valve)
S036 - Source fan inverter min speed
S037 - Source fan inverter max speed
S039 - Defrost start threshold
S040 - Defrost start threshold reset
S041 - Defrost start delay
S042 - Defrost end threshold
S044 - Defrost begin delay before actuating the 4 way valve
S045 - Defrost ending delay after actuating the 4 way valve
S046 - Defrost min duration
S047 - Defrost max duration
S048 - Dripping duration
S049 - Post dripping duration
S050 - Delay between defrosts
C049 - Low pressure alarm start delay
C050 - Low pressure alarm run delay
F024 - Heater 1 manual mode (0=AUTO, 1=OFF, 2=ON)
F025 - Heater 2 manual mode (0=AUTO, 1=OFF, 2=ON)
S053 - Defrost synchronisation type (0=Independent,
1=Separate, 2=Simultaneous)
S054 - Delta press. to reverse the 4 way valve
iom-clicsa-cf-eng