Daikin Clima-Flex CLIC STAND ALONE Series Installation, Operation And Maintenance Manual page 39

Air-cooled scroll compressor chiller water generator unit
Table of Contents

Advertisement

Mapping Table
Index Size Acronym
DataType
758
1
Hc43
USINT
759
1
Hc44
USINT
760
1
Hc45
USINT
761
1
Hc47
USINT
762
1
AI_CfgLim-
USINT
Max_Grp2_Slv
763
1
AI_CfgLim-
USINT
Max_Grp1_Slv
764
1
UnitTyp_Lim-
USINT
Max
765
2
U084
REAL
767
2
SEtU
REAL
769
1
U088
USINT(0..2)
770
2
F026
REAL
772
2
U085
REAL
774
2
U086
REAL
776
2
U087
REAL
818
2
U090
REAL
820
2
U091
REAL
822
2
U092
REAL
817
1
U089
USINT(0..2)
788
1
Hc90
USINT
789
1
Hc91
USINT
Input Register
Index Size Acronym
0
2
HuP1
2
2
HuP2
4
2
H1C1
6
2
H1C2
8
2
H2C1
10
2
H2C2
12
2
dSt1
14
2
Sct1
16
2
dSt2
18
2
Sct2
20
2
dSP1
22
2
ScP1
24
2
Cnd1
26
2
EuP1
28
2
dSP2
30
2
ScP2
32
2
Cnd2
34
2
EuP2
36
2
HSP1
38
1
C045
39
1
UnitCompTyp_Lim-
Max
40
2
HFn1
42
2
HFn2
46
2
SEtA
48
2
SSH1
50
1
Opn1
51
2
SSH2
53
1
Opn2
54
2
rUSr
56
2
dUSr
www.clima-flex.com
Min
Max
Init
R/W
Value
Value
Value
R/W 0
R/W 0
R/W 0
R/W 0
R/W 10
R/W 8
R/W 4
R/W 23
R/W 23
R/W 0
R/W -40
R/W 2
R/W 5
R/W 20
R/W 0
R/W 0
R/W 100
R/W 0
0
8
R/W 0
0
8
R/W 0
Min
Max
DataType
R/W
Value
Value
UDINT
R
UDINT
R
UDINT
R
UDINT
R
UDINT
R
UDINT
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
REAL
R
UDINT
R
UINT
R
USINT
R
UDINT
R
UDINT
R
REAL
R
REAL
R
UINT
R
REAL
R
UINT
R
REAL
R
REAL
R
UoM
Description
Hc43 - Analogue input 3 confi g. on Secondary board (0= Not
used, 1= Source water delivery temp., 2= Outside temp., 3=
Discharge temp., 4= Condensing temp., 5= Suction temp., 6=
Evaporation temp., 7=Common delivery temp., 8= Delivery
water evap.2 temp.)
Hc44 - Analogue input 4 confi g. on Secondary board (0= Not used,
1= Source water delivery temp., 2= Outside temp., 3= Discharge
temp., 4= Condensing. temp., 5= Suction temp., 6= Evaporation
temp., 7= Condensing press., 8= Evaporating press., 9= Common
delivery temp., 10= Delivery water evap.2 temp.)
Hc45 - Analogue input 5 confi g. on Secondary board (0= Not used,
1= Source water delivery temp., 2= Outside temp., 3= Discharge
temp., 4= Condensing. temp., 5= Suction temp., 6= Evaporation
temp., 7= Condensing press., 8= Evaporating press., 9= Common
delivery temp., 10= Delivery water evap.2 temp.)
Hc47 - Analogue input 7 confi g. on Secondary board (0= Not
used, 1= Source water delivery temp., 2= Outside temp., 3=
Discharge temp., 4= Condensing temp., 5= Suction temp., 6=
Evaporation temp., 7=Common delivery temp., 8= Delivery
water evap.2 temp.)
AI_CfgLimMax_Grp2 - Lim max probe group 2 secondary
AI_CfgLimMax_Grp1 - Lim max probe group 1 secondary
UnitTyp_LimMax - Lim max unit type
CELSIUS
U084 - Automatic changever threshold (type 1) (°C)
CELSIUS
SEtU - Automatic changeover set point (type 2,3) (°C)
U088 - Frost heater position
CELSIUS
F026 - Compressor cut-off by outside temperature
DELTAKEL-
U085 - Automatic changeover deadband (°C)
VIN
CELSIUS
U086 - Automatic changeover set point low limit (°C)
CELSIUS
U087 - Automatic changeover set point high limit (°C)
PERCENT
U090 - Analogue capacity request off set
PERCENT
U091 - Analogue capacity request min value
PERCENT
U092 - Analogue capacity request max value
U089 - Analogue capacity request input type (0=0-5V, 1=0-
10V, 2=4-20mA)
HC90 - Display value selection - Large area
Hc91 - Display value selection - Small area
Init
UoM
Description
Value
0
HOUR
HuP1 - User pump 1 operating hours
0
HOUR
HuP2 - User pump 2 operating hours
0
HOUR
H1C1 - Comp.1 circ.1 operating hours
0
HOUR
H1C2 - Comp.2 circ.1 operating hours
0
HOUR
H2C1 - Comp.1 circ.2 operating hours
0
HOUR
H2C2 - Comp.2 circ.2 operating hours
0
CELSIUS
dSt1 - Discharge temp. probe on circ.1
0
CELSIUS
Sct1 - Suction temp. on circ.1
0
CELSIUS
dSt2- Discharge temp. probe on circ.2
0
CELSIUS
Sct2 - Suction temp. on circ.2
0
BAR
dSP1 - Discharge press. probe on circ.1
0
BAR
ScP1 - Suction press. on circ.1
0
CELSIUS
Cnd1 - Cond. temp. probe (or press. probe converted
value) on circ.1
0
CELSIUS
EuP1 - Evap. temp. probe (or press. probe converted
value) on circ.1
0
BAR
dSP2 - Discharge press. probe on circ.2
0
BAR
ScP2 - Suction press. on circ.2
0
CELSIUS
Cnd2 - Cond. temp. probe (or press. probe converted
value) on circ.2
0
CELSIUS
EuP2 - Evap. temp. probe (or press. probe converted
value) on circ.2
0
HOUR
HSP1 - Source pump 1 operating hours
0
C045 - Refrigerant type (3=R407C, 4=R410a, 6=R290,
10=R744, 22=R32)
0
UnitCompTyp_LimMax - Limit max of UnitCompTyp
variable
0
HOUR
HFn1 - Source fan 1 circ.1 operating hours
0
HOUR
HFn2 - Source fan 1 circ.2 operating hours
0
CELSIUS
SEtA - Actual set point used by temp. control
0
DELTAKELVIN SSH1 - Suction superheat on circ.1
0
PERCENT
Opn1 - EEV position on circ.1
0
DELTAKELVIN SSH2 - Suction superheat on circ.2
0
PERCENT
Opn2 - EEV position on circ.2
0
CELSIUS
rUSr - Return water temp. from user
0
CELSIUS
dUSr - Delivery water temperature to user
39