iC7 Series PROFINET
Operating Guide
Table 13: General Connectivity Parameters
Menu in-
Parameter
dex
10.3.1.2
Fieldbus profile
10.3.1.3
Fieldbus Fault
Response
10.3.1.4
No Fieldbus
Connection Re-
sponse
10.3.1.6
Process Data
Timeout Time
10.3.1.12
Process Data
Timeout Re-
sponse
10.3.1.13
Process Data
Timeout Con-
trol Place
Table 14: Event Descriptions
Value
Info
Warning
Fault, ramp to coast
Danfoss A/S © 2023.06
Param-
Value
eter
num-
ber
1301
•
iC Speed Profile (default)
•
PROFIdrive Standard telegram 1
1303
•
Info (default)
•
Warning
•
Fault, Ramp to Coast
•
Fault, coast
See
Table 14
for descriptions of the events.
1327
•
Info (default)
•
Warning
•
Fault, Ramp to Coast
•
Fault, coast
See
Table 14
for descriptions of the events.
1340
0.05–18000 s (Default value: 1.00 s)
1341
•
Info
•
Warning
•
Warning – Change Control Place
•
Warning – Change Control Place Persistent
•
Fault, Ramp to coast
•
Fault (default)
See
Table 14
for descriptions of the events.
112
•
Local control (default)
•
Fieldbus control
•
I/O control
•
Advanced control
See
Table 15
for descriptions of the control places.
Description
The event is logged in the event log.
The drive issues a warning.
The drive issues a fault, ramps down, and coasts.
PROFINET Configuration
Description
Select the fieldbus profile. The se-
lection affects the interpretation of
the control word and status word.
Select the behavior when a field-
bus fault, for example loss of I/O
connection occurs.
Select the response in case there is
no fieldbus connection.
Set the timeout time. If process da-
ta is not received within the time
set, a process data timeout is trig-
gered.
Select the response in case there is
no fieldbus connection.
Select the alternate control place
to be used if there is a fieldbus
timeout. This is only valid with a
timeout warning or info.
AQ408626183394en-000101 / 136R0280 | 25
Need help?
Do you have a question about the iC7 Series and is the answer not in the manual?
Questions and answers