iC7 Series PROFINET
Operating Guide
Table 13: General Connectivity Parameters
Menu in-
Parameter
dex
10.3.1.2
Fieldbus profile
10.3.1.3
Fieldbus Fault
Response
10.3.1.4
No Fieldbus
Connection Re-
sponse
10.3.1.6
Process Data
Timeout Time
10.3.1.12
Process Data
Timeout Re-
sponse
10.3.1.13
Process Data
Timeout Con-
trol Place
Table 14: Event Descriptions
Value
Info
Warning
Fault, ramp to coast
Danfoss A/S © 2023.06
Param-
Value
eter
num-
ber
1301
iC Speed Profile (default)
PROFIdrive Standard telegram 1
1303
Info (default)
Warning
Fault, Ramp to Coast
Fault, coast
See
Table 14
for descriptions of the events.
1327
Info (default)
Warning
Fault, Ramp to Coast
Fault, coast
See
Table 14
for descriptions of the events.
1340
0.05–18000 s (Default value: 1.00 s)
1341
Info
Warning
Warning – Change Control Place
Warning – Change Control Place Persistent
Fault, Ramp to coast
Fault (default)
See
Table 14
for descriptions of the events.
112
Local control (default)
Fieldbus control
I/O control
Advanced control
See
Table 15
for descriptions of the control places.
Description
The event is logged in the event log.
The drive issues a warning.
The drive issues a fault, ramps down, and coasts.
PROFINET Configuration
Description
Select the fieldbus profile. The se-
lection affects the interpretation of
the control word and status word.
Select the behavior when a field-
bus fault, for example loss of I/O
connection occurs.
Select the response in case there is
no fieldbus connection.
Set the timeout time. If process da-
ta is not received within the time
set, a process data timeout is trig-
gered.
Select the response in case there is
no fieldbus connection.
Select the alternate control place
to be used if there is a fieldbus
timeout. This is only valid with a
timeout warning or info.
AQ408626183394en-000101 / 136R0280 | 25