COMMISSIONING

ADJUSTING COOLER SETTINGS

Within the SETTINGS menu of the MagIQtouch Controller is the
COOLER sub-heading. Here various settings of the cooler can
be adjusted.
ABOUT APPLIANCE
Displays information such as model number, serial number and
software version for all coolers connected to the controller.
MANUAL DRAIN
Turns cooler off and drains the tank.
COOLING CORE FLUSH
Turns cooler off and runs pump for a specified amount of time.
DRAIN AND DRY
Cooler will drain and fan will run for 1 hour every day at a
specified time.
WATER MANAGER
Select the preferred water management method:
• Salinity Measurement - replaces water when salinity level
reaches set point.
• Timed Drain - drains the tank after 8 tank fill cycles or every
65 minutes (system dependant).
WEATHERSEAL OPEN SPEED
The cooler fan will turn on at the specified weatherseal opening
speed for the first 10 seconds each time it starts up. It will then
return to the set fan speed.
PRE-WET
When COOL mode is activated, the pump will run for 90
seconds before the fan is switched on.
SALINITY LEVEL
Sets the salinity level at which the tank will drain in "SALINITY
MEASUREMENT" mode. It is recommended the cooler are set
to LOW (2305 uS/cm)
TANK DRAIN DELAY
Sets the time delay before the drain valve opens after the pump
in the cooler is turned off.
AUTOMATIC CLEAN FUNCTION
Run a Cooling Core Flush and Tank Drain based on cooler
operating time.
ILL1664-A
859741-L CW3 INSTALLATION MANUAL
| 23