Cooler Control Options; Magiqtouch Controls; Group Installations - Seeley CW3 Installation Manual

Microcore indirect evaporative cooler
Table of Contents

Advertisement

COOLER CONTROL OPTIONS

MAGIQTOUCH CONTROLS

This cooler is compatible with a wide range of MagIQtouch
control solutions, including Wall Controllers, Building
Management System (BMS) Controllers and Sensor
Accessories.
MAGIQTOUCH WALL CONTROL
MS1 BMS INDUSTRIAL CONTROL
Refer to the Installation & Operation Manual for the selected
MagIQtouch product for setup instructions.
Whichever control option is being used, the inbuilt water
management and fault monitoring features are always
functional.
Note! If a BMS is used, it is suggested that technicians obtain
a MagIQtouch Wall Controller as a tool for use during servicing.
The MagIQtouch Controller provides additional user and
technician functions.
20 |
859741-L CW3 INSTALLATION MANUAL
'ON'
COMMUNICATIONS
CABLE
ILL2792-A

GROUP INSTALLATIONS

Each cooler electronics has a terminating resistor dipswitch
located near the communications port. Ensure all cooler
electronics dipswitches are set to "OFF" except for the last
cooler in the series. The last cooler dipswitch should be
switched to "ON" to ensure communication reliabilty.
Note: The terminating resistor dipswitch position is set to OFF
by default.
Terminating dipswitch
ON position
ON
OFF position
'ON'
TOTAL COOLERS
CABLE LENGTH
= >20M / 66'
PER INSTALLATION = 60 QTY
MAXIMUM CABLE LENGTH FROM WALL CONTROLLER TO LAST APPLAINCE = 500M / 1640'
Coolers are supplied with a 20m (66') control cable. Longer
cable lengths are available for order via Seeley International.
Important! The maximum cable length allowed from the
MagIQtouch Controller to the first cooler is 40 metres (131'),
between each subsequent cooler 40 metres (131') up to a
maximum distance of 500 metres (1650').
Note! The maximum length for the wall control cable to travel
alongside the power cable is 10m (33')
Failure of the product or components to operate correctly due
to modification to supplied cables, or the use of non-approved
cables will NOT be accepted under the Manufacturer's
Warranty.
Terminating dipswitch
(Alternative orientation)
OFF position
ON position
Terminating Dipswitch
location on CW
OFF
OFF
NOTE : ALL CABLES ARE 20M
SUPPLIED EX FACTORY
MAX CABLE LENGTH
CABLE LENGTH
TO WALL CONTROL
= >20M / 66'
= <40M / 131'
ILL3816-B