2.6.3 Dual Inlet Return Piping

The standard dual inlet connections allow these units to be configured with a separate cooler
return temperature zone, rather than blending high and low return temperature zones. Utilizing
the dual return capability, these boilers can take further advantage of the condensing
capabilities. When configured with a lower return temperature zone or AERCO SmartPlate,
thermal efficiency can improve by up to 6% (Based on an 80 °F (26.7 °C) minimum return water
temperature at full fire. Lower return temperatures are possible which would yield even greater
efficiency gains. The maximum temperature differential across the boiler heat exchanger is 100
°F (37.8 °C).
To use the secondary inlet, pipe the warmer return water to the secondary (upper) inlet and
the cooler return water to the primary (lower) inlet. If the flow through both the primary and the
secondary return is constant, then the combined minimum flows must equal the specified
minimum flow of the boiler. If the flow through either of the inlet returns is intermittent, then the
minimum flow through one of the return connections must always equal the specified minimum
flow of the boiler. Contact your AERCO representative for additional information.
OMM-115_D
GF-200
5/9/2019
2" NATURAL GAS OR
1" PROPANE INLET
HOT WATER
OUTLET
(SUPPLY)
AIR INLET
SECONDARY WATER INLET
(WARMER WATER RETURN)
PRIMARY
WATER INLET
(COOLER WATER
RETURN)
EXHAUST MANIFOLD
CONDENSATE DRAIN