Benchmark 750-3000 Installation & Startup Manual
FORWARD

FOREWORD

The AERCO Benchmark (BMK) 750, 1000, 1500, 2000, 2500, and 3000 natural gas and
propane fueled boilers are modulating and condensing units. They represent a true industry
advance that meets the needs of today's energy and environmental concerns. Designed for
application in any closed loop hydronic system, the Benchmark's modulating capability relates
energy input directly to fluctuating system loads. These BMK models provide extremely high
efficiency operation and are ideally suited for modern low temperature, as well as, conventional
heating systems.
IMPORTANT!
Unless otherwise specified all descriptions provided in this document apply to the Benchmark
Series of boiler.
The Benchmark models operate within the input and output ranges listed below. All
measurements apply to both natural gas and propane models, unless otherwise specified.
Benchmark Boiler Intake and Output Ranges
MODEL
MINIMUM
BMK 750
50,000 (14.6 kW)
BMK 1000 50,000 (14.6 kW)
BMK 1500 75,000 (22 kW)
BMK 2000 100,000 (29.3 kW)
BMK 2500 167,000 (48.9 kW)
BMK 3000 200,000 (58.6 kW)
The output of the boiler is a function of the unit's firing rate (valve position) and return water
temperature.
When installed and operated in accordance with this Instruction Manual, the BMK 750 – 2000
and 5000 & 6000 comply with the NO
Management District (SCAQMD), Rule 1146.2. In addition, the BMK 2500 – 6000 comply with
the Bay Area Air Quality Management District regulation 9, Rule 7.
Whether used in singular or modular arrangements, the BMK boilers offer the maximum venting
flexibility with minimum installation space requirements. These boilers are Category II and IV,
positive pressure appliances. Single and/or multiple breeched units are capable of operation in
the following vent configurations:
• Room Combustion Air:
o Vertical Discharge
o Horizontal Discharge
• Ducted Combustion Air:
o Vertical Discharge
o Horizontal Discharge
These boilers are capable of being vented utilizing Polypropylene and AL29-4C vent systems. In
addition, the BMK 750 & 1000 models are also approved for PVC and CPVC, vent systems.
OMM-115_D
GF-200
5/9/2019
INPUT RANGE (BTU/HR.)
MAXIMUM
750,000 (220 kW)
1,000,000 (293 kW) 48,300 (14.2 kW)
1,500,000 (440 kW) 64,500 (18.9 kW)
2,000,000 (586 kW) 86,000 (25.2 kW)
2,500,000 (732 kW) 144,000 (42.2 kW)
3,000,000 (879 kW) 174,000 (51.0 kW)
emission standards outlined in: South Coast Air Quality
x
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
OUTPUT RANGE (BTU/HR.)
MINIMUM
47,750 (14.0 kW)
716,250 (210 kW)
968,000 (284 kW)
1,395,000 (409 kW)
1,860,000 (545 kW)
2,395,000 (702 kW)
2,874,000 (842 kW)
MAXIMUM
Page 5 of 126