SECTION 4 – INITIAL START-UP
TO
AIR/FUEL
VALVE
MANUAL
SHUT-OFF
VALVE
HIGH GAS
PRESSURE
SWITCH
Figure 4-1d: BMK 3000 1/4 Inch Gas Plug Location

4.2.3 Accessing the Analyzer Probe Port

The unit contains a 1/4" NPT port on the side of the exhaust manifold as shown in Figure 4-2a
and 4-2b. Prepare the port for the combustion analyzer probe as follows:
Analyzer Probe Port Access Instructions
1. Refer to Figure 4-2a or 4-2b and remove the 1/4" NPT plug from the exhaust manifold.
2. If necessary, adjust the stop on the combustion analyzer probe so it will extend mid-way
into the flue gas flow. DO NOT install the probe at this time.
OMM-115_D
GF-200
5/9/2019
LEAK DETECTION
BALL VALVE
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
126
1/4" NPT PLUG
(Install manometer
here for Combustion
Calibration)
(P/N 22171 shown)
NATURAL
GAS INLET
SSOV
LOW GAS
PRESSURE
SWITCH