58
INSTRUCTION HANDBOOK
Circuit breakers in UL version characterized by a current rating up to 2500A show differences
at level of parts involved in this disassembly phase, consequently here below an analogous
section is provided for these circuit breakers.
Tools
Torx key
UL version - Current rating up to 2500A
215
No. 15
By means of the torx key (size 15) unscrew the
No. 40
10 screws fixing the claw contacts to the pole.
217
Manually remove the spacers located below the
claw contacts.
216
Push the claw contacts as indicated by the
arrows and after manually remove the claw
contacts.
218
By means of the torx key (size 40) unscrew
the 6 screws fixing the terminals and their
protections to the pole.