Download Print this page

ABB EMAX 2 E4.2 Instruction Handbook Manual page 56

Advertisement

56
INSTRUCTION HANDBOOK
Circuit breakers in UL version characterized by a current rating of 3200A show differences
at level of parts involved in this disassembly phase, consequently here below an analogous
section is provided for these circuit breakers.
Tools
UL version - Current rating 3200A
Torx key
210
No. 15
By means of the torx key (size 15) unscrew the
No. 40
10 screws fixing the claw contacts to the pole.
212
By means of the torx key (size 40) unscrew
the 6 screws fixing the terminals and their
protections to the pole.
211
Push the claw contacts as indicated by the
arrows and after manually remove the claw
contacts.
213
Manually remove the terminals from the pole.

Advertisement

loading