Running Modes - Deif AGC 150 Operator's Manual

Hide thumbs Also See for AGC 150:
Table of Contents

Advertisement

Standard
The control buttons and LEDs are shown.
If you stop the genset, the motor/generator symbols are not shown.
Standard with genset
The control buttons and LEDs are shown.
If you the stop the genset, the motor/generator symbols are shown
in red.
Guided
Active control buttons and LEDs are shown inactive are not shown.
Example: The AGC 150 Stand-alone is in SEMI-AUTO mode, and the
genset is not operating. Only the start button is shown, as this is
the only possible action.
Guided with genset
Active control buttons, LEDs and the motor/generator symbols are
shown, inactive are not shown.
Example: The AGC 150 Stand-alone is in SEMI-AUTO mode. The
genset is not operating. The only possible action is to start the
genset, and so only the start button and the red motor/generator
symbols are shown.
All Mimic settings
Red breaker symbol:
• Breaker position failure
• Breaker close failure
2.4

Running modes

The controller has three different running modes, a block mode and a test mode. Push the Shortcut
Running Modes to see the running modes and block mode. Configure the test mode in Parameters > Power set points
> Test. To select the test mode push the Shortcut
Mode
Description
The controller automatically starts and stops (and connects and disconnects) the genset. The operator
AUTO
cannot start a sequence manually.
The controller cannot automatically start, stop, connect and disconnect the genset or open and close the
SEMI-AUTO
mains breaker. The operator can start these sequences using the buttons on the controller, Modbus
commands or the digital inputs. If the genset starts in semi-auto mode, it will operate at nominal values.
The operator can use the digital increase/decrease inputs (if they are configured) and the Start and Stop
MANUAL
buttons. When the genset starts in manual mode, it will start without subsequent regulation.
Operator's manual 4189341311B EN
button and select Start Test.
button and select
Page 7 of 22