No.
Name
13
Breaker symbols
14
Generator
15
Engine
16
Stop
17
Start
18
Load symbol
2.2

Display settings

To adjust for ambient lighting, configure the display settings.
Parameters > Basic settings > Controller settings > Display > Display control
Parameter
Text
9151
Backlight dimmer
9152
Green LEDs dimmer
9153
Red LEDs dimmer
9154
Contrast level
9155
Sleep mode timer
9156
Enable (Sleep mode timer)
9157
Alarm Jump
9158
Engineering units
NOTE
* Low numbers are minimum brightness and high numbers are maximum brightness.
2.3

Mimic function

With the mimic function you can select how the control buttons and LEDs are shown on the controller's display.
Parameters > Basic settings > Controller settings > Display > LED mimic
Parameter no.
6082
Operator's manual 4189341311B EN
Function
Green: Breaker is closed.
Red: Breaker failure.
Green: Generator voltage and frequency are OK. The controller can close the breaker.
Green flashing: The generator voltage and frequency are OK, but the V&Hz OK timer is still
running. The controller cannot close the breaker.
Red: The generator voltage is too low to measure.
Green: There is running feedback.
Green flashing: The engine is getting ready.
Red: The engine is not running, or there is no running feedback.
Stops the genset if SEMI-AUTO or Manual is selected.
Starts the genset if SEMI-AUTO or Manual is selected.
Green: The supply voltage and frequency are OK.
Red: Supply voltage/frequency failure.
Item
LED mimic
Range
0 to 15 *
1 to 15 *
1 to 15 *
-20 to +20
1 to 1800 s
OFF
ON
OFF
ON
Bar/Celsius
PSI/Fahrenheit
Default
12
15
15
0
60 s
ON
ON
Bar/Celsius
Range
Standard with genset
Standard
Guided with genset
Guided